Baseline HVAC Systems
This page defines the baseline HVAC systems required by ASHRAE 90.1 Performance Rating Method (PRM) Appendix G. The system selection is based on building type, number of floors, floor area, and climate zone.
System Selection Table
ASHRAE 90.1 Baseline HVAC Systems (Systems 1-13)
1
PTAC
Packaged Terminal AC
Constant Volume
Direct Expansion
Hot Water Boiler
Residential; Small buildings
2
PTHP
Packaged Terminal Heat Pump
Constant Volume
Direct Expansion
Electric Heat Pump
Residential with electric heating
3
PSZ-AC
Packaged Single Zone AC
Constant Volume
Direct Expansion
Gas Furnace
Small non-residential; ≤3 floors; <2,300 m²
4
PSZ-HP
Packaged Single Zone Heat Pump
Constant Volume
Heat Pump
Electric Heat Pump
All climates with electric heating
5
PVAV with Reheat
Packaged VAV Reheat
VAV
Direct Expansion
Hot Water Reheat
Mid-size buildings; 4-5 floors; 2,300-14,000 m²
6
PVAV with PFP
Packaged VAV with PFP Boxes
VAV
Direct Expansion
Electric Resistance
Mid-size buildings; electric heating
7
VAV Reheat
VAV with Reheat
VAV
Chilled Water
Hot Water Reheat
Large buildings; >5 floors; >14,000 m²
8
VAV PFP Boxes
VAV with PFP Boxes
VAV
Chilled Water
Electric Resistance
Large buildings; electric heating
9
Gas Furnace
Warm Air Furnace (Gas)
Constant Volume
None
Gas Furnace
Heating and Ventilation Only
10
Electric Furnace
Warm Air Furnace (Electric)
Constant Volume
None
Electric Resistance
Heating and Ventilation Only (Electric)
11
SZ-VAV
Single Zone VAV
VAV
Chilled Water
Variable (Climate Dependent)
Medium buildings; single thermal zone
12
SZ-CV-HW
Single Zone Constant Volume
Constant Volume
Chilled Water
Hot Water Boiler
Medium buildings; constant volume system
13
SZ-CV-ER
Single Zone Constant Volume
Constant Volume
Chilled Water
Electric Resistance
Medium buildings; electric heating
Detailed System Descriptions
System 1: PTAC (Packaged Terminal Air Conditioner)
Component Configuration:
Supply Fan: Single-speed constant volume fan
Cooling: Direct expansion (DX) cooling coil
Heating: Hot water heating coil connected to building hot water loop
Controls: Thermostat with heating/cooling setpoint
EnergyPlus Objects:
Fan:OnOfforFan:ConstantVolume(supply fan)Coil:Cooling:DX:SingleSpeed(cooling coil)Coil:Heating:Water(heating coil)ZoneHVAC:PackagedTerminalAirConditioner
Application:
Residential buildings (apartments, hotels, dormitories)
Small commercial buildings
One unit per thermal zone
Climate Zone Application:
All climate zones with fossil fuel heating (CZ 3B-8)
Electric heating alternative (PTHP) for CZ 0-3A
System 2: PTHP (Packaged Terminal Heat Pump)
Component Configuration:
Supply Fan: Single-speed constant volume fan
Cooling/Heating: Air-source heat pump with DX coil
Supplemental Heating: Electric resistance coil for heating
EnergyPlus Objects:
Fan:OnOfforFan:ConstantVolume(supply fan)Coil:Cooling:DX:SingleSpeed(cooling coil)Coil:Heating:DX:SingleSpeed(heat pump heating)Coil:Heating:Electric(supplemental heating)ZoneHVAC:PackagedTerminalHeatPump
Application:
Residential buildings in mild to warm climates
Electric heating alternative to PTAC
One unit per thermal zone
Climate Zone Application:
CZ 0-3A (mild climates)
System 3: PSZ-AC (Packaged Rooftop Air Conditioner)
Component Configuration:
Supply Fan: Single-speed constant volume fan
Cooling: Direct expansion cooling coil
Heating: Gas-fired furnace
Controls: Thermostat; economizer for cooling
EnergyPlus Objects:
Fan:ConstantVolume(supply fan)Coil:Cooling:DX:SingleSpeed(cooling coil)Coil:Heating:GasorCoil:Heating:Fuel(furnace)AirLoopHVACwith outdoor air damper
Application:
Small non-residential buildings
3 floors or fewer
Floor area < 2,300 m² (24,800 ft²)
Can serve multiple zones from single rooftop unit
Climate Zone Application:
CZ 3B-8 (fossil fuel heating)
System 4: PSZ-HP (Packaged Rooftop Heat Pump)
Component Configuration:
Supply Fan: Single-speed constant volume fan
Cooling/Heating: Air-source heat pump with DX coil
Supplemental Heating: Electric resistance coil
EnergyPlus Objects:
Fan:ConstantVolume(supply fan)Coil:Cooling:DX:SingleSpeed(cooling coil)Coil:Heating:DX:SingleSpeed(heat pump heating)Coil:Heating:Electric(supplemental heating)AirLoopHVACwith outdoor air damper
Application:
Small non-residential buildings with electric heating
Alternative to PSZ-AC in areas without gas availability
Climate Zone Application:
CZ 0-3A (mild climates with electric heating)
System 5: PVAV with Reheat (Packaged VAV with Reheat)
Component Configuration:
Supply Fan: Variable volume fan with VFD control
Cooling: Direct expansion cooling coil
Zone Heating: Hot water reheat coils in each zone
Controls: VAV terminal units with heating/cooling logic
EnergyPlus Objects:
Fan:VariableVolume(supply fan with VFD)Coil:Cooling:DX:SingleSpeed(cooling coil)AirTerminal:SingleDuct:VAV:Reheat(VAV terminal with reheat)Coil:Heating:Water(zone reheat coils)PlantLoop(hot water loop)
Application:
Mid-size non-residential buildings
4-5 floors or 5 floors with 2,300-14,000 m² floor area
Multiple thermal zones served by single air loop
VAV terminals reduce air volume at part load
Climate Zone Application:
CZ 3B-8 (fossil fuel heating via hot water loop)
Key Features:
Demand-controlled ventilation capability
Energy recovery potential
VFD saves energy at part load
System 6: PVAV with PFP Boxes (Parallel Fan Power Boxes)
Component Configuration:
Supply Fan: Variable volume fan with VFD control
Cooling: Direct expansion cooling coil
Zone Heating: Parallel fan-powered boxes with electric resistance or hot water heating
Controls: VAV terminal units with parallel fan operation
EnergyPlus Objects:
Fan:VariableVolume(supply fan)Coil:Cooling:DX:SingleSpeed(cooling coil)AirTerminal:SingleDuct:ParallelPIU:Reheat(parallel fan power box)Coil:Heating:ElectricorCoil:Heating:Water(terminal heating)
Application:
Mid-size buildings with electric heating preference
Improves comfort in perimeter zones
Parallel fan boxes maintain circulation
Climate Zone Application:
CZ 0-3A (electric heating)
System 7: VAV with Reheat (Central Chilled Water System)
Component Configuration:
Supply Fan: Variable volume fan with VFD control
Cooling: Central chiller with chilled water loop
Zone Heating: Hot water reheat coils in VAV terminals
Central Heating: Gas or oil-fired boiler
Condenser Heat Rejection: Cooling tower
EnergyPlus Objects:
Fan:VariableVolume(supply fan)Coil:Cooling:Water(cooling coil on air loop)AirTerminal:SingleDuct:VAV:Reheat(VAV terminal with reheat)Chiller:Electric:EIR(centrifugal or screw chiller)Boiler:HotWater(heating boiler)CoolingTower:SingleSpeedorCoolingTower:TwoSpeedPlantLoop(chilled water and condenser water loops)
Application:
Large buildings
5 floors or >14,000 m² floor area
Most efficient for large multi-zone buildings
Serves multiple air handling units
Climate Zone Application:
CZ 3B-8 (fossil fuel heating)
Key Features:
Centralized cooling for multiple zones
Demand-controlled ventilation
Energy recovery with heat wheel capability
VFD reduces fan energy at part load
System 8: VAV with PFP Boxes (Central Chilled Water)
Component Configuration:
Supply Fan: Variable volume fan with VFD control
Cooling: Central chiller with chilled water loop
Zone Heating: Parallel fan-powered boxes with electric resistance heating
Central Heating: Not used (zone heating only)
Condenser Heat Rejection: Cooling tower
EnergyPlus Objects:
Fan:VariableVolume(supply fan)Coil:Cooling:Water(cooling coil)AirTerminal:SingleDuct:ParallelPIU:Reheat(parallel fan power box)Coil:Heating:Electric(electric resistance in terminals)Chiller:Electric:EIR(central chiller)CoolingTower:SingleSpeedPlantLoop(chilled water and condenser water)
Application:
Large buildings with electric heating
Provides zone-level heating control
No central boiler required
Climate Zone Application:
CZ 0-3A (electric heating)
System 9: Gas Furnace (Heating and Ventilation Only)
Component Configuration:
Supply Fan: Single-speed constant volume fan
Heating: Gas-fired furnace (no cooling)
No mechanical cooling system
Controls: Thermostat for heating setpoint
EnergyPlus Objects:
Fan:ConstantVolume(supply fan)Coil:Heating:GasorCoil:Heating:Fuel(furnace)AirLoopHVAC(ventilation and heating only)
Application:
Buildings with heating only requirements
Unheated or naturally ventilated spaces
No summer cooling needed (storage facilities, warehouses)
Climate Zone Application:
CZ 3B-8 (fossil fuel heating)
System 10: Electric Furnace (Heating and Ventilation Only)
Component Configuration:
Supply Fan: Single-speed constant volume fan
Heating: Electric resistance heater
No mechanical cooling system
EnergyPlus Objects:
Fan:ConstantVolume(supply fan)Coil:Heating:Electric(electric resistance heating)AirLoopHVAC(ventilation and heating only)
Application:
Heated storage spaces
Ventilation-only with heating backup
Electric heating alternative to System 9
Climate Zone Application:
CZ 0-3A (electric heating)
System 11: SZ-VAV (Single Zone VAV System)
Component Configuration:
Supply Fan: Variable volume fan with VFD control
Cooling: Chilled water cooling coil (central plant)
Heating: Climate zone dependent
CZ 0-2B: Electric resistance heating
CZ 3A and warmer: Hot water reheat or electric resistance
Controls: Zone thermostat with VAV modulation
EnergyPlus Objects:
Fan:VariableVolume(supply fan)Coil:Cooling:Water(cooling coil)Coil:Heating:WaterorCoil:Heating:Electric(heating)AirLoopHVAC:UnitarySystemorAirLoopHVAC
Application:
Medium-size buildings with single thermal zone control
Flexible heating fuel based on climate
Climate Zone Application:
CZ 0-2B: Electric heating
CZ 3A+: Hot water or electric heating
System 12: SZ-CV-HW (Single Zone Constant Volume with Hot Water)
Component Configuration:
Supply Fan: Single-speed constant volume fan
Cooling: Chilled water cooling coil
Heating: Hot water heating coil
Controls: Thermostat with continuous operation
EnergyPlus Objects:
Fan:ConstantVolume(supply fan)Coil:Cooling:Water(cooling coil)Coil:Heating:Water(heating coil)AirLoopHVAC:UnitarySystem
Application:
Medium-size buildings
Simpler control without VAV
Constant air volume regardless of load
Climate Zone Application:
All climates with fossil fuel heating availability
System 13: SZ-CV-ER (Single Zone Constant Volume with Electric Resistance)
Component Configuration:
Supply Fan: Single-speed constant volume fan
Cooling: Chilled water cooling coil
Heating: Electric resistance heating coil
Controls: Thermostat with continuous operation
EnergyPlus Objects:
Fan:ConstantVolume(supply fan)Coil:Cooling:Water(cooling coil)Coil:Heating:Electric(electric resistance)AirLoopHVAC:UnitarySystem
Application:
Medium-size buildings with electric heating
No fossil fuel boiler required
Simple constant volume control strategy
Climate Zone Application:
CZ 0-3A (electric heating climates)
System Selection Decision Tree
Component Specifications by System
Cooling System Efficiencies
DX Cooling
Packaged Unit
Variable by capacity
EIR from AHRI ratings
Chiller
Centrifugal
0.5-0.6 kW/ton
Chiller:Electric:EIR
Chiller
Screw
0.55-0.65 kW/ton
Chiller:Electric:EIR
Cooling Tower
Single Speed
Approach = 6.7°C
CoolingTower:SingleSpeed
Heating System Efficiencies
Gas Furnace
0.80 (80%)
Coil:Heating:Gas
Gas Boiler
0.85 (85%)
Boiler:HotWater
Electric Resistance
1.0 (100%)
Coil:Heating:Electric
Heat Pump (Heating)
3.0 COP
Coil:Heating:DX:SingleSpeed
Fan Specifications
Constant Volume
On/Off or Always On
400-600 Pa
Fan:ConstantVolume
Variable Volume
VFD with 0.5-1.0 minimum
400-600 Pa
Fan:VariableVolume
EnergyPlus Simulation Inputs
Air Loop Configuration
Plant Loop Configuration
Climate Zone Definitions
0A
Very Hot/Humid
Minimal
Significant
Electricity
0B
Very Hot/Dry
Minimal
Significant
Electricity
1A
Hot/Humid
Low
Significant
Electricity
1B
Hot/Dry
Low
Significant
Electricity
2A
Hot/Humid
Moderate
Significant
Electricity
2B
Hot/Dry
Moderate
Significant
Electricity
3A
Warm/Humid
Moderate
Moderate
Gas
3B
Warm/Dry
Moderate
Moderate
Gas
3C
Warm/Marine
Moderate
Low
Gas
4
Mixed/All
Moderate-High
Moderate
Gas
5
Cool
High
Moderate
Gas
6
Cool
High
Low-Moderate
Gas
7
Very Cool
Very High
Low
Gas
8
Subarctic
Very High
Low
Gas
Key Controls and Setpoints
Thermostat Setpoints (PRM Baseline)
Heating Setpoint: 21°C (70°F)
Cooling Setpoint: 24°C (75°F)
Deadband: Minimum 1.7°C (3°F)
VAV Terminal Minimum Flow
Default Minimum: 50% of design air flow
Can be reduced to: 30% with justification
Based on: Ventilation requirements per ASHRAE 62.1
Supply Air Temperature (SAT) Reset
Warmest Zone: Increase SAT based on warmest zone heating load
Outside Air: SAT reset based on outdoor temperature
Typical Range: 13-21°C (55-70°F)
Economizer Operation
Dry Bulb Cutoff: 21°C outdoor (varies by climate)
Enthalpy Cutoff: When outdoor air enthalpy exceeds return air
Integrated Mode: Damper modulation for cooling assistance