System Total R-value Calculations (CIBSE Guide A)
The Better Building Floor System R-Value calculation approach has been derived from CIBSE Guide A Section 3.5 Ground Floors and Basements. The system calculates thermal resistance (R-value, in m²·K·W⁻¹), which is the inverse of thermal transmittance (U-value, in W·m⁻²·K⁻¹).
Floor Classification
Following the guidelines of CIBSE Guide A, there are four floor configurations:
Ground Contact with edge insulation (Section 3.5.3, Equation 3.22)
Ground Contact without edge insulation (Section 3.5.2, Equation 3.21)
Suspended Floor - insulated (Section 3.5.5.2, Equation 3.31)
Suspended Floor - uninsulated (Section 3.5.5.1, Table 3.20 or Equations 3.28-3.30)
Calculation Procedure
The calculation follows this hierarchical approach:
Initialise as ground contact floor - establish base parameters
Collect relevant components for the specific floor type
Check for edge insulation or suspension - determine if CIBSE Equation 3.22 (edge insulated) or Equations 3.28-3.31 (suspended) apply
Apply appropriate calculation method to determine the final U-value, then convert to R-value (R = 1/U)
Parameter Collection
Ground Contact Parameters
Required Inputs
All floor types require the following fundamental inputs:
Floor area
A_fg
m²
Equation 3.19
Floor perimeter (exposed)
p_f
m
Equation 3.19
Ground thermal conductivity
λ_g
W·m⁻¹·K⁻¹
Table 3.17
Surrounding wall thickness
d_w
m
Equation 3.23
Floor thermal resistance
R_f
m²·K·W⁻¹
Section 3.3
Critical Definitions
Characteristic Dimension (B′)
CIBSE Equation 3.19:
Where:
B′ = characteristic dimension of the floor (m)
A_fg = floor area (m²)
p_f = exposed perimeter of floor (m) - includes only perimeter exposed to external (unconditioned) conditions
Floor Thermal Resistance (R_f)
For ground contact floors: Includes only continuous insulation layers above, below, or within the floor slab, excluding the structural slab itself and surface resistances (CIBSE Section 3.5.2)
Surface resistances (R_si and R_se) are handled separately in the U-value calculation
Total Equivalent Thickness (d_ef)
Where:
d_ef = total equivalent thickness (m)
d_w = thickness of wall surrounding the floor (m)
λ_g = thermal conductivity of ground (W·m⁻¹·K⁻¹)
R_si = 0.17 m²·K·W⁻¹ (internal surface resistance)
R_f = thermal resistance of floor insulation (m²·K·W⁻¹)
R_se = 0.04 m²·K·W⁻¹ (external surface resistance)
Edge Insulation Parameters
Edge insulation is evaluated via two mechanisms per CIBSE Equation 3.22:
Option 1: Direct Edge Insulation
Horizontal or vertical insulation applied at the floor perimeter, characterized by:
Edge insulation width (D) or depth (D′), in metres
Edge insulation thermal resistance (R_n), in m²·K·W⁻¹
Note: Currently unavailable in Better Building
Option 2: Thermally Improved Wall

The surrounding wall provides edge insulation effect when:
Where:
λ_w = thermal conductivity of wall (W·m⁻¹·K⁻¹)
λ_g = thermal conductivity of ground (W·m⁻¹·K⁻¹)
Collected Parameters
Wall thermal resistance (R_w) in m²·K·W⁻¹
Wall thickness (d_w) in m
Wall depth below ground (D′) in m - as shown above.
Equivalent Edge Insulation Width
This check is automatically performed for all non-suspended floors.
Suspended Floor Parameters

Floor Classification Criteria
A floor is classified as suspended when the user specifies:
Where h_f = height of floor above external ground level (m), as shown above.
Additional Required Inputs
Per CIBSE Equation 3.30:
Wind speed at 10m height
v_w
m·s⁻¹
3 m·s⁻¹ (UK average)
Wind shielding factor
f_w
-
0.02 (sheltered), 0.05 (suburban), 0.10 (exposed)
Ventilation opening area per unit perimeter
α
m²·m⁻¹
0.0015 or 0.003
Wall U-value (underfloor space)
U_u
W·m⁻²·K⁻¹
1.7 (uninsulated masonry)
Height of floor above ground
h_f
m
Typically 0.5 m
Suspended Floor Types
Uninsulated Suspended Floor
Reference: CIBSE Table 3.20 or Equations 3.28-3.30
Calculate U_fs using combined thermal transmittance approach
Floor thermal resistance (R_f) treated as center-of-panel calculation
Include surface resistances: R_si = R_se = 0.17 m²·K·W⁻¹ on both sides
U_f calculated from: U_f = 1 / (R_si + R_f + R_se)
Insulated Suspended Floor
Reference: CIBSE Equation 3.31
First calculate uninsulated U_fs (as above, assuming R_f = 0.2 m²·K·W⁻¹)
Then apply actual floor thermal resistance
Floor R_f calculated as thermally-bridged assembly per AS/NZS 4859.2:2018
Exclude surface resistances from R_f (these are accounted for in Equation 3.31)
Final U_fsi calculated per Equation 3.31
Complete CIBSE Equations
Ground Contact Floor Equations
Equation 3.21: Ground Contact (No Edge Insulation)
Where:
U_g = thermal transmittance of ground floor (W·m⁻²·K⁻¹)
λ_g = thermal conductivity of ground (W·m⁻¹·K⁻¹)
B′ = characteristic dimension (m) from Equation 3.19
d_ef = total equivalent thickness (m)
A_fg = floor area (m²)
p_f = exposed perimeter (m)
R-value conversion:
Equation 3.22: Ground Contact with Edge Insulation
Where all parameters are as Equation 3.21, plus:
Ψ_ge = linear thermal transmittance for edge insulation (m)
Equation 3.23: Horizontal Edge Insulation
Where:
D = width of horizontal edge insulation (m)
R_n = thermal resistance of edge insulation per unit area (m²·K·W⁻¹)
d_ef = total equivalent thickness as before (m)
λ_g = thermal conductivity of ground (W·m⁻¹·K⁻¹)
Equation 3.24: Vertical Edge Insulation
Where:
D′ = depth of vertical edge insulation below floor level (m)
Other parameters as above
Low Conductivity Foundation Wall
For walls shown in Figure 3.12:
Suspended Floor Equations
Equation 3.28: Combined Thermal Transmittance
Where:
U_fs = combined thermal transmittance of uninsulated suspended floor (W·m⁻²·K⁻¹)
U_f = thermal transmittance of the floor itself (W·m⁻²·K⁻¹)
U_fg = thermal transmittance for heat flow through ground (W·m⁻²·K⁻¹)
U_eu = equivalent thermal transmittance for wall and ventilation losses (W·m⁻²·K⁻¹)
Equation 3.29: Equivalent Ground Thickness (Suspended Floors)
Where:
d_eg = total equivalent thickness of ground for suspended floor (m)
d_w = thickness of wall surrounding floor (m)
λ_g = thermal conductivity of ground (W·m⁻¹·K⁻¹)
R_si = internal surface resistance = 0.17 m²·K·W⁻¹
R_ig = thermal resistance of insulation between floor and ground (m²·K·W⁻¹) - typically 0 for uninsulated
R_se = external surface resistance = 0.17 m²·K·W⁻¹ (note: 0.17 for both sides in suspended floor)
Equation 3.30: Wall and Ventilation Losses
Where:
U_eu = equivalent thermal transmittance for walls and ventilation (W·m⁻²·K⁻¹)
h_f = height of floor above external ground level (m)
U_u = thermal transmittance of walls surrounding underfloor space (W·m⁻²·K⁻¹)
B′ = characteristic dimension (m)
α = area of ventilation openings per unit perimeter (m²·m⁻¹)
v_w = average wind speed at 10 m height (m·s⁻¹)
f_w = wind shielding factor (dimensionless)
Wind Shielding Factor (f_w) Values
Sheltered location (city centre): f_w = 0.02
Average location (suburban): f_w = 0.05
Exposed location (rural): f_w = 0.10
Floor Thermal Transmittance (U_f) for Uninsulated Suspended Floors
For uninsulated suspended floors, surface resistances are applied to both sides:
Where R_si = R_se = 0.17 m²·K·W⁻¹
Ground Thermal Transmittance (U_fg) for Suspended Floors
Calculate using Equation 3.21 format but with d_eg from Equation 3.29 substituted for d_ef:
Equation 3.31: Insulated Suspended Floor
Where:
U_fsi = thermal transmittance of insulated suspended floor (W·m⁻²·K⁻¹)
U_fs = combined thermal transmittance of uninsulated floor from Equation 3.28 (W·m⁻²·K⁻¹)
R_f = thermal resistance of actual floor excluding surface resistances (m²·K·W⁻¹)
0.2 = assumed thermal resistance used in standard uninsulated calculation (m²·K·W⁻¹)
Calculation Procedure
Calculate U_fs using Equations 3.28-3.30 with R_f = 0.2 m²·K·W⁻¹
Calculate actual R_f for the insulated floor (excluding surface resistances)
Apply Equation 3.31 to determine U_fsi
Convert to R-value: R = 1 / U_fsi
Thermal Bridging Calculations
Bridged Thermal Resistance
For thermally bridged floors (e.g., timber joists with insulation between):
Where:
R_b = combined thermal resistance of bridged section (m²·K·W⁻¹)
P_m = proportion of area occupied by insulation (dimensionless)
R_m = thermal resistance of insulation section (m²·K·W⁻¹)
P_n = proportion of area occupied by structural members (dimensionless)
R_n = thermal resistance of structural section (m²·K·W⁻¹)
Note: P_m + P_n = 1
Total Floor Resistance
As calculated per AS/NZS 4859.2:2018 methodology, excluding surface resistances.
CIBSE Table 3.20: U-values for Uninsulated Suspended Floors
Table Assumptions
This table provides U-values for uninsulated suspended floors based on the following fixed parameters:
Thermal resistance of floor
R_f = 0.2
m²·K·W⁻¹
Average wind velocity
v_w = 3
m·s⁻¹
Wind shielding factor
f_w = 0.05
-
Wall U-value (underfloor space)
U_u = 1.7
W·m⁻²·K⁻¹
Height of floor above ground
h_f = 0.5
m
Exposure
Average (suburban)
-
Table 3.20 Data
U-values (W·m⁻²·K⁻¹) for stated soil type and ventilation opening
Ratio p_f / A_fg (m⁻¹)
Clay/silt
Sand/gravel
Homogeneous rock
α = 0.0015
α = 0.003
α = 0.0015
α = 0.003
α = 0.0015
α = 0.003
0.05
0.16
0.17
0.19
0.20
0.27
0.28
0.10
0.27
0.29
0.32
0.33
0.43
0.44
0.15
0.36
0.38
0.42
0.43
0.54
0.55
0.20
0.44
0.46
0.49
0.51
0.63
0.64
0.25
0.50
0.52
0.56
0.58
0.70
0.71
0.30
0.56
0.58
0.62
0.64
0.76
0.77
0.35
0.61
0.63
0.67
0.69
0.81
0.82
0.40
0.65
0.68
0.72
0.74
0.85
0.87
0.45
0.69
0.72
0.76
0.78
0.89
0.91
0.50
0.73
0.76
0.79
0.82
0.92
0.94
0.55
0.76
0.79
0.83
0.85
0.95
0.97
0.60
0.79
0.83
0.86
0.88
0.98
1.00
0.65
0.82
0.85
0.88
0.91
1.00
1.02
0.70
0.85
0.88
0.91
0.94
1.03
1.05
0.75
0.87
0.91
0.93
0.96
1.05
1.07
0.80
0.90
0.93
0.95
0.98
1.06
1.09
0.85
0.92
0.95
0.97
1.00
1.08
1.11
0.90
0.94
0.97
0.99
1.02
1.10
1.12
0.95
0.96
0.99
1.01
1.04
1.11
1.14
1.00
0.98
1.01
1.03
1.06
1.13
1.15
Note: The row for p_f/A_fg = 0.45 is highlighted in bold as this value is used in the worked example below.
Using Table 3.20
Step-by-Step Procedure
Calculate the perimeter-to-area ratio:
Identify the soil type:
Clay/silt
Sand/gravel
Homogeneous rock
Determine ventilation opening area:
α = 0.0015 m²·m⁻¹ (standard ventilation)
α = 0.003 m²·m⁻¹ (increased ventilation)
Look up U_fs value from the appropriate column and row
For insulated floors: Use the looked-up U_fs in Equation 3.31
Interpolation Guidelines
If your calculated p_f/A_fg ratio falls between table values:
Linear interpolation is acceptable for intermediate values
For greater accuracy, use the full equations (3.28-3.30)
Example Lookup
For the worked example:
p_f/A_fg = 0.45 m⁻¹
Soil: Clay/silt
Ventilation: α = 0.0015 m²·m⁻¹
Result: U_fs = 0.69 W·m⁻²·K⁻¹
Calculation Methodology
Decision Flowchart
Step 1: Determine Floor Type
Ground Contact Floors
Method 1: No Edge Insulation
Calculate B′ using Equation 3.19
Calculate d_ef: d_ef = d_w + λ_g × (0.17 + R_f + 0.04)
Calculate U_g using Equation 3.21
Convert: R = 1 / U_g
Method 2: With Edge Insulation
Calculate B′ using Equation 3.19
Calculate d_ef as above
Calculate Ψ_ge using Equation 3.23 or 3.24 (or equivalent for low-conductivity wall)
Calculate U using Equation 3.22
Convert: R = 1 / U
Suspended Floors
Method 3: Uninsulated Suspended Floor
Option A: Using Table 3.20 (if parameters match)
Calculate p_f / A_fg ratio
Look up U_fs from Table 3.20
Convert: R = 1 / U_fs
Option B: Using Full Equations (if parameters differ)
Calculate B′ using Equation 3.19
Calculate d_eg using Equation 3.29 (typically R_ig = 0)
Calculate U_fg using Equation 3.21 format with d_eg
Calculate U_eu using Equation 3.30
Calculate U_f = 1 / (0.17 + R_f + 0.17)
Calculate U_fs using Equation 3.28
Convert: R = 1 / U_fs
Method 4: Insulated Suspended Floor
Obtain U_fs for uninsulated case using Table 3.20 or Equations 3.28-3.30 (with R_f = 0.2)
Calculate actual R_f (thermally-bridged if applicable, excluding surface resistances)
Apply Equation 3.31 to determine U_fsi
Convert to R-value: R = 1 / U_fsi
Technical Implementation Notes
Surface Resistance Treatment
Ground contact
0.17
0.04
Included in d_ef calculation
Suspended uninsulated
0.17
0.17
Included in U_f calculation
Suspended insulated
-
-
Handled by Equation 3.31 adjustment factor
Thermal Bridging Considerations
Ground Contact Floors
Not typically considered
Continuous insulation assumed in R_f
Structural elements ignored in thermal resistance calculation
Suspended Insulated Floors
Must calculate bridged R_b for joists/beams
Use AS/NZS 4859.2:2018 methodology
Account for proportion of structural elements vs. insulation
Perimeter Definition Guidelines
What to Include
All perimeter exposed to unconditioned space
External walls
Walls to unheated spaces
What to Exclude
Party walls between conditioned spaces
Internal divisions within heated area
Walls to heated adjacent rooms
Measurement Location
Measure at floor level
Not at foundation level
Use internal dimensions
Table 3.20 Usage Guidelines
When to Use Table 3.20
Use the lookup table when ALL of these conditions are met:
R_f = 0.2 m²·K·W⁻¹
α = 0.0015 or 0.003 m²·m⁻¹
v_w = 3 m·s⁻¹
f_w = 0.05 (suburban exposure)
U_u = 1.7 W·m⁻²·K⁻¹
h_f = 0.5 m
Soil type matches one of the three columns
When to Use Full Equations
Use Equations 3.28-3.30 when parameters differ significantly from table assumptions:
Different floor heights (h_f ≠ 0.5 m)
Different exposures (f_w ≠ 0.05)
Different wind speeds (v_w ≠ 3 m·s⁻¹)
Different ventilation rates (α not 0.0015 or 0.003)
Different wall constructions (U_u ≠ 1.7 W·m⁻²·K⁻¹)
Non-standard floor thermal resistance (R_f ≠ 0.2)
Unit Conversions
U-value to R-value
Examples
0.20
5.00
0.30
3.33
0.50
2.00
0.69
1.45
1.00
1.00
Worked Example
Example: Insulated Suspended Timber Floor
Given Parameters
Floor Geometry:
Dimensions: 9.5 m × 8.2 m
Construction type: Suspended timber floor
Floor Construction:
19 mm chipboard (λ = 0.14 W·m⁻¹·K⁻¹)
50 mm × 100 mm joists at 400 mm centers (λ = 0.14 W·m⁻¹·K⁻¹)
100 mm insulation between joists (λ = 0.04 W·m⁻¹·K⁻¹)
Site Conditions:
Ventilation: α = 0.0015 m²·m⁻¹
Soil type: Clay
Exposure: Average (suburban)
Step 1: Calculate Floor Parameters
Step 2: Obtain U_fs from Table 3.20
Lookup parameters:
Clay/silt soil
α = 0.0015 m²·m⁻¹
p_f/A_fg = 0.45 m⁻¹
From Table 3.20:
Note: Since all parameters match the table assumptions (h_f = 0.5 m, v_w = 3 m·s⁻¹, f_w = 0.05, U_u = 1.7 W·m⁻²·K⁻¹), we can use the table lookup directly.
Step 3: Calculate Actual Floor Resistance
Chipboard Layer
Bridged Section (Joists + Insulation)
Insulation path:
Joist path:
Combined bridged resistance:
Total Floor Resistance
Step 4: Apply Equation 3.31
Final Result
U-value:
R-value:
Quick Reference Summary
Equation Selection Guide
Ground contact, no edge insulation
0
No
3.21
Ground contact, with edge insulation
0
Yes
3.22 + 3.23/3.24
Suspended, uninsulated
>0
N/A
Table 3.20 or 3.28-3.30
Suspended, insulated
>0
N/A
3.31 (uses Table 3.20 or 3.28-3.30)
Key Parameter Values
Internal surface resistance
R_si
0.17
m²·K·W⁻¹
External surface resistance (ground)
R_se
0.04
m²·K·W⁻¹
External surface resistance (suspended)
R_se
0.17
m²·K·W⁻¹
Wind speed
v_w
3
m·s⁻¹
Wind shielding (suburban)
f_w
0.05
-
Ventilation opening
α
0.0015 or 0.003
m²·m⁻¹
Underfloor wall U-value
U_u
1.7
W·m⁻²·K⁻¹
Floor height
h_f
0.5
m
Last updated
Was this helpful?

