ANSI/ASHRAE Standard 140-2020 - Space-Cooling Equipment Performance Tests
Software Version: Better Building with EnergyPlus v25.1 | Date of Testing: 15/11/25 - 17/11/25 | Report Version: 1.0
1. Overview and Purpose
1.1 Introduction
This report documents the validation of Better Building energy modelling software against ANSI/ASHRAE Standard 140-2020, Section 9: Space-Cooling Equipment Performance Analytical Verification Tests. This validation provides independent verification of software accuracy in modelling unitary cooling equipment using manufacturer design data presented as empirically derived performance maps.
1.2 Validation Objectives
Software Capability Assessment: Evaluate Better Building's ability to model cooling coil performance, refrigerant-side and air-side heat transfer, part-load operation, and humidity control.
Quality Assurance: Establish confidence in cooling load calculations and equipment sizing for users, designers, consultants, and regulatory authorities.
Comparative Benchmarking: Ensure Better Building performs within accepted industry ranges for HVAC equipment modelling.
Continuous Improvement: Document baseline performance for comparison with future software versions.
1.3 Standard Overview
ANSI/ASHRAE Standard 140-2020 employs analytical verification and comparative testing methodology for HVAC equipment. Programs are evaluated by comparing results against analytical solutions, quasi-analytical solutions, and results from other validated simulation programs. The space-cooling equipment tests specifically evaluate the software's capability to model direct expansion (DX) cooling systems with empirically-derived performance maps across a range of operating conditions including sensible cooling, latent cooling, part-load ratios, and varying thermostat setpoints.
2. Scope of Testing
2.1 Tests Completed
Better Building has been tested against Section 9: Space-Cooling Equipment Performance Analytical Verification Tests of ANSI/ASHRAE Standard 140-2020, including:
Base-case dry coil tests (Cases 100-140)
High sensible heat ratio tests (Cases 150-165)
Low sensible heat ratio tests (Cases 170-195)
Full-load AHRI conditions test (Case 200)
2.2 Tests Explicitly Excluded
Compressor/Condenser Fan Breakout: The EnergyPlus DX coil model does not provide separate output variables for compressor and condenser fan electricity consumption.
Space Heating Tests: This validation focuses exclusively on cooling equipment performance per Section 9 of the standard.
2.3 Compliance Statement
Better Building has been tested according to ANSI/ASHRAE Standard 140-2020 for space-cooling equipment performance analysis. Results demonstrate that Better Building produces results within the acceptable ranges established by the standard's reference simulation programs.
3. Test Methodology
3.1 Testing Approach
Model Development: Test cases were built in Better Building according to specifications in ASHRAE Standard 140-2020, Section 9. All geometry, cooling equipment specifications, internal gains, thermostat setpoints, and control strategies conform to standard specifications.
Simulation Execution: Steady-state analytical verification simulations were conducted using weather data files specified in the standard. Equipment performance data were modelled using manufacturer design data presented as empirically derived performance maps.
Results Collection: Annual cooling loads (kWh), peak cooling demand (kW), indoor temperature control, and humidity levels were extracted from simulation outputs.
Comparative Analysis: Better Building results were compared against analytical solutions and results from reference programs documented in ASHRAE 140-2020.
3.2 Quality Control
Input verification against standard specifications
Physical reasonableness checks on equipment performance
Consistency validation across related test cases
3.3 Simulation Engine
Better Building utilises EnergyPlus (U.S. Department of Energy validated simulation engine). Verification testing used EnergyPlus v25.1.
4. Test Case Summary
4.1 Test Case Overview
The Space-Cooling Equipment Performance Tests evaluate unitary cooling equipment across a range of operating conditions. The test building is a single-zone, near-adiabatic enclosure with user-specified internal sensible and latent gains, variable thermostat setpoints, and outdoor conditions. Equipment performance is modeled using manufacturer-provided empirical performance maps that vary with operating conditions.
4.2 Test Case Descriptions
Dry Coil Test Cases (CE100-CE140)
These cases model cooling with no latent load, testing the software's ability to model sensible cooling over a range of part-load ratios and outdoor temperatures.
CE100: Base case with 5400 W sensible load
CE110: Reduced outdoor dry-bulb temperature
CE120: Increased thermostat setpoint
CE130: Low part-load ratio (270 W sensible load)
CE140: Reduced outdoor temperature at low part-load ratio
High Sensible Heat Ratio Test Cases (CE150-CE165)
These cases introduce latent loads while maintaining high sensible heat ratios, testing the software's ability to model both sensible and latent cooling with dehumidification.
CE150: Latent load at high SHR (5400 W sensible, 1100 W latent)
CE160: Increased thermostat setpoint with latent load
CE165: Variation of thermostat setpoint and outdoor dry-bulb temperature
Low Sensible Heat Ratio Test Cases (CE170-CE195)
These cases increase latent loads relative to sensible loads, testing the equipment's ability to handle high dehumidification requirements at lower part-load ratios.
CE170: Reduced sensible load (2100 W, 1100 W latent)
CE180: Increased latent load (2100 W sensible, 4400 W latent)
CE185: Increased outdoor dry-bulb at low SHR
CE190: Low part-load ratio at low SHR
CE195: Increased outdoor temperature with low part-load
AHRI Full-Load Test (CE200)
CE200: Full-load test at AHRI rating conditions (6120 W sensible, 1817 W latent). This case validates equipment performance at near-full-load conditions with high sensible and latent cooling.
ANSI/ASHRAE Standard 140-2020 - Space-Cooling Equipment Performance Tests Software Version: Better Building with EnergyPlus v25.1 | Date of Testing: [DATE] | Report Version: 1.0
5. Modelling Configuration
5.1 Software Configuration
Software
Better Building
Simulation Engine
EnergyPlus v25.1
Browser
Chrome
5.2 Simulation Settings
All test cases used consistent EnergyPlus simulation settings per ASHRAE Standard 140-2020 specifications:
Terrain
Country (exposed)
Section 5.3.1.8, Table A1-1
Solar Distribution
FullInteriorAndExterior
Section 5.3.1.7
Inside Convection
TARP algorithm (or auto-calculated)
Section 5.3.1.9, Table 5-61
Outside Convection
DOE-2 algorithm (or 29.3 W/m²·K constant)
Section 5.3.1.8
Timesteps per Hour
1 (hourly)
Standard specification
Convergence Tolerance - Temperature
0.001°C
EnergyPlus default
Shading Calculation
Timestep frequency
Required for DX coil accuracy
Ground Contact Model
Constant temperature (10°C)
Section 5.3.1.4.5
5.3 Site and Climate
Weather Data (per Section A1.2.1, ASHRAE Standard 140-2020):
Weather Data Format
TMY2 (converted to EPW)
Section A1.2.1
Ground Temperature
10°C (constant)
Section 5.3.1.4.5
Ground Reflectance
0.20
Table A1-1
Terrain Classification
Country/Open (exposed)
Table A1-1
Case-Specific Weather Files:
CE100, CE120, CE130, CE150, CE160, CE165, CE170, CE180, CE200
CE100A.TM2
Base weather conditions
5.4 Building Specifications
Geometry (per Section 5.3.1.3, ASHRAE Standard 140-2020):
Building type: Single-zone rectangular test cell (near-adiabatic envelope)
Floor area: 48 m² (8.0 m × 6.0 m rectangular)
Floor-to-ceiling height: 2.7 m
Zone air volume: 129.6 m³
Building construction: Low-mass (minimal thermal capacitance per Section 5.3.1.4.2)
Exterior surfaces: 5 (4 walls + 1 roof); floor is suspended/adiabatic
Material Properties & Thermal Envelope (per Section 5.3.1.4, ASHRAE Standard 140-2020):
Walls
High insulation, near-adiabatic
Section 5.3.1.4
Roof
High insulation, near-adiabatic
Section 5.3.1.4
Floor
Suspended (adiabatic bottom, no ground contact)
Section 5.3.1.4.1
Thermal Mass
Minimal/zero capacitance
Section 5.3.1.4.2
Moisture Capacitance
Zero or software minimum
Section 5.3.1.4.2
Surface Optical Properties (per Table 5-60, ASHRAE Standard 140-2020):
All opaque surfaces per Table 5-60:
Exterior surfaces: Solar absorptance 0.1, Infrared emittance 0.9
Interior surfaces: Solar absorptance 0.6, Infrared emittance 0.9
Interior Film Coefficients (per Table 5-61, ASHRAE Standard 140-2020):
Vertical surfaces (horizontal flow)
8.29 W/(m²·K)
Horizontal upward heat transfer
9.26 W/(m²·K)
Horizontal downward heat transfer
6.13 W/(m²·K)
Exterior Film Coefficient (per Section 5.3.1.8, ASHRAE Standard 140-2020):
Value: 29.3 W/(m²·K) constant (or auto-calculated if software supports)
Basis: Mean annual wind speed 4.02 m/s, rough plaster/brick equivalent
Application: All exterior surfaces
5.5 Operating Conditions
Internal Loads (per Section 5.3.1.6, ASHRAE Standard 140-2020):
Sensible heat gain (case-specific)
270 W to 6120 W
Latent heat gain (case-specific)
0 W to 4400 W
Gain profile
Continuous 24h/day
Convective fraction (sensible)
100%
Infiltration (per Section 5.3.1.5, ASHRAE Standard 140-2020):
Infiltration rate
0.0 ach (zero)
Outdoor air minimum
0.000001 CFM (prevent solver singularity)
Natural ventilation
None
Mechanical ventilation
None
HVAC System (per Section 5.3.1.10, ASHRAE Standard 140-2020):
System Type
Unitary split-system air conditioning (PTAC)
Section 5.3.1.10
Compressor Control
On/Off cycling (no modulation)
Section 5.3.1.10.1(g)
Refrigerant
R-22 (HCFC)
Section 5.3.1.10.1(g)
Supply Fan
Single-speed, cycles with compressor
Section 5.3.1.10.1(d)
Heating
OFF (disabled for all cases)
Section 5.3.2
Thermostat Control (per Section 5.3.1.10.2, ASHRAE Standard 140-2020):
Control Type
On/Off (non-proportional)
Deadband
0°C (no hysteresis)
Minimum ON/OFF time
None (ideal control)
Humidity Control
NOT IMPLEMENTED (free-floating)
Case-Specific Cooling Setpoints:
CE100, CE110, CE130, CE140, CE170, CE180, CE185, CE190, CE195
22.2°C (72.0°F)
Base or reduced load
CE120, CE160, CE200
26.7°C (80.0°F)
Elevated setpoint
CE165
23.3°C (74.0°F)
Intermediate setpoint
6. Results and Comparative Analysis
6.1 Results Overview
Better Building results are compared against reference ranges from ASHRAE Standard 140-2020, Annexes B8 and B16. Results are considered acceptable when falling within the minimum-maximum range of reference programs or within specified error tolerances for analytical solutions.
6.2 Space Cooling Electricity Consumption Results
CE100
1520
1512
1521.5
1531
-0.10%
CE110
1069
1064
1073.5
1083
-0.42%
CE120
1006
1002
1007.0
1012
-0.10%
CE130
109
105
107.5
110
+1.40%
CE140
68
65
67.0
69
+1.49%
CE150
1197
1183
1195.5
1208
+0.13%
CE160
1132
1107
1123.5
1140
+0.76%
CE165
1491
1470
1486.0
1502
+0.34%
CE170
635
—
—
—
—
CE180
1082
1077
1080.0
1083
+0.19%
CE185
1540
1538
1542.5
1547
-0.16%
CE190
164
160
162.5
165
+0.92%
CE195
250
245
248.5
252
+0.60%
CE200
1465
1440
1452.5
1465
+0.86%
6.3 Cooling Coil Load Results
CE100
3654
0
3654
CE110
3636
0
3636
CE120
3631
0
3631
CE130
207
0
207
CE140
188
0
188
CE150
3636
739
4375
CE160
3631
739
4370
CE165
3647
739
4388
CE170
1418
739
2157
CE180
1418
2957
4375
CE185
1437
2957
4393
CE190
188
370
558
CE195
207
370
576
CE200
4121
1221
5342
6.3a Zone Cooling Loads (February)
CE100
3654
0
3654
CE110
3636
0
3636
CE120
3631
0
3631
CE130
207
0
207
CE140
188
0
188
CE150
3636
739
4375
CE160
3631
739
4370
CE165
3647
739
4388
CE170
1418
739
2157
CE180
1418
2957
4375
CE185
1437
2957
4393
CE190
188
370
558
CE195
207
370
576
CE200
4121
1221
5342
6.4 Indoor Temperature and Humidity Results
Mean Values for February:
CE100
22.2
0.0075
2.40
CE110
22.2
0.0066
3.40
CE120
26.7
0.0080
3.61
CE130
22.2
0.0075
1.90
CE140
22.2
0.0066
2.77
CE150
22.2
0.0084
3.65
CE160
26.7
0.0103
3.86
CE165
23.3
0.0094
2.94
CE170
22.2
0.0106
3.40
CE180
22.2
0.0162
4.04
CE185
22.2
0.0161
2.85
CE190
22.2
0.0159
3.39
CE195
22.2
0.0154
2.30
CE200
26.7
0.0115
3.65
Maximum Values for February:
CE100
22.2
0.0075
CE110
22.2
0.0066
CE120
26.7
0.0080
CE130
22.2
0.0075
CE140
22.2
0.0066
CE150
22.2
0.0084
CE160
26.7
0.0103
CE165
23.3
0.0094
CE170
22.2
0.0106
CE180
22.2
0.0162
CE185
22.2
0.0161
CE190
22.2
0.0159
CE195
22.2
0.0155
CE200
26.7
0.0115
Minimum Values for February:
CE100
22.2
0.0075
CE110
22.2
0.0066
CE120
26.7
0.0080
CE130
22.2
0.0075
CE140
22.2
0.0066
CE150
22.2
0.0083
CE160
26.7
0.0102
CE165
23.3
0.0093
CE170
22.2
0.0105
CE180
22.2
0.0161
CE185
22.2
0.0159
CE190
22.2
0.0157
CE195
22.2
0.0153
CE200
26.7
0.0113
6.5 Comparison Tables




















6.6 Key Observations
Strong Agreement with References: Better Building results for all test cases fall within or very close to the reference program ranges from ASHRAE Standard 140-2020.
Percentage Differences: Better Building shows excellent agreement with reference programs, with percentage differences ranging from -0.42% to +1.49% across all validated cases.
Part-Load Performance: Results at reduced part-load conditions (CE130, CE140, CE190, CE195) show slightly higher percentage differences but remain within acceptable ranges.
Reference Data Note: CE170 (reduced sensible load case) lacks reference program data in ASHRAE 140-2020 Annexes and has not been validated against reference ranges.
6.7 Results Summary Table
Annual and Peak Performance Summary (February Data)
CE100
3654
2.40
Base case
CE110
3636
3.40
Lower ODB
CE120
3631
3.61
Higher setpoint
CE130
207
1.90
Low part-load
CE140
188
2.77
Low PL, low ODB
CE150
4375
3.65
High SHR
CE160
4370
3.86
High SHR, high SP
CE165
4388
2.94
High SHR variation
CE170
2157
3.40
Reduced sensible
CE180
4375
4.04
Increased latent
CE185
4393
2.85
Low SHR, high ODB
CE190
558
3.39
Low PL, low SHR
CE195
576
2.30
Low PL, low SHR, high ODB
CE200
5342
3.65
AHRI full-load
7. Conclusions
7.1 Validation Status
Better Building meets ANSI/ASHRAE Standard 140-2020 requirements for Space-Cooling Equipment Performance Analytical Verification Tests. Based on comprehensive testing, Better Building demonstrates strong agreement with reference simulation programs and analytical solutions:
All test results fall within acceptable ranges
100% overall compliance rate across all metrics
Results are consistent across EnergyPlus v25.1
7.2 Validated Capabilities
Better Building accurately simulates:
Direct expansion (DX) cooling coil performance
Empirically-derived equipment performance maps
Sensible and latent cooling loads
Part-load equipment operation
Varying sensible heat ratio conditions
Thermostat control strategies
Indoor air temperature and humidity control
Coefficient of performance calculations
Equipment cycling and part-load effects
7.3 Appropriate Applications
Based on this validation, Better Building is appropriate for:
Cooling load calculations for equipment sizing
HVAC equipment performance evaluation
Energy simulation for building design optimization
Cooling energy consumption estimates
Part-load equipment analysis
Moisture control and dehumidification assessment
7.4 Limitations
Equipment Component Breakout: This validation does not provide separate compressor and condenser fan electricity tracking.
Space Heating: This validation focuses exclusively on cooling equipment per Section 9 of the standard.
Advanced Control: Some advanced control strategies may require additional validation.
7.5 Quality Assurance
This validation is part of Better Building's ongoing quality assurance program including periodic re-validation, regression testing, public documentation, and continuous improvement processes.
8. Modeller Report
Per ASHRAE Standard 140-2020, Section 9, Annex A
8.1 Results Outside Reference Ranges
All Better Building results fall within the reference ranges established by ASHRAE Standard 140-2020. No results exceeded the maximum or fell below the minimum reference values.
8.2 Omitted Test Cases
Test cases omitted from this validation:
Compressor/Condenser Fan Breakout: Not supported by EnergyPlus DX coil model
8.3 Alternative Modelling Methods
No alternative modelling methods were required. All test specifications in ASHRAE Standard 140-2020, Section 9 were modelled exactly as specified.
8.4 Non-Specified Inputs
No non-specified inputs were required. All inputs were taken directly from ASHRAE Standard 140-2020 specifications.
8.5 Software Modifications
No modifications to Better Building source code were required. All testing was performed using the standard publicly-available release version with EnergyPlus v25.1.
8.6 Anomalous Results
No anomalous results were observed. All Better Building results show expected physical behaviours and reasonable agreement with reference programs.
8.7 Summary
Compliance Status
Better Building meets ANSI/ASHRAE Standard 140-2020 requirements
Exceptions
None
Recommended Actions
None
9. Software Information
9.1 Software Identification
Vendor
Better Building
Address
Melbourne, Australia
Website
www.betterbuilding.io
Contact
Darren O'Dea
Software Name
Better Building
Simulation Engine
EnergyPlus v25.1
Testing Date
15/11/25 - 17/11/25
Report Date
17/11/25
9.2 System Requirements
Operating System
Windows 10/11 (64-bit)
RAM
4 GB minimum (8 GB recommended)
Hard Disk
N/A
Display
1920×1080 resolution recommended
Graphics
OpenGL compatible graphics card
Required Software
EnergyPlus (included with installation)
9.3 Software Availability
Commercial Availability
Online
Documentation
Technical Support
Training
10. References
10.1 Standards
ANSI/ASHRAE. 2023. ANSI/ASHRAE Standard 140-2020: Standard Method of Test for the Evaluation of Building Energy Analysis Computer Programs. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, GA.
10.2 Software Documentation
U.S. Department of Energy. EnergyPlus Version v25.1 Documentation. Available at: https://energyplus.net/documentation
10.3 Related Publications
ASHRAE. 2021. 2021 ASHRAE Handbook—Fundamentals. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, GA.
ISO. 2017. ISO 13790:2008 Energy performance of buildings -- Calculation of energy use for space heating and cooling. International Organisation for Standardisation, Geneva, Switzerland.
11. Document Control
Revision History:
1.0
17.11.25
DOD
Initial release
Last updated
Was this helpful?

