ANSI/ASHRAE Standard 140-2020 - Space-Cooling Equipment Performance Tests

Software Version: Better Building with EnergyPlus v25.1 | Date of Testing: 15/11/25 - 17/11/25 | Report Version: 1.0

1. Overview and Purpose

1.1 Introduction

This report documents the validation of Better Building energy modelling software against ANSI/ASHRAE Standard 140-2020, Section 9: Space-Cooling Equipment Performance Analytical Verification Tests. This validation provides independent verification of software accuracy in modelling unitary cooling equipment using manufacturer design data presented as empirically derived performance maps.

1.2 Validation Objectives

Software Capability Assessment: Evaluate Better Building's ability to model cooling coil performance, refrigerant-side and air-side heat transfer, part-load operation, and humidity control.

Quality Assurance: Establish confidence in cooling load calculations and equipment sizing for users, designers, consultants, and regulatory authorities.

Comparative Benchmarking: Ensure Better Building performs within accepted industry ranges for HVAC equipment modelling.

Continuous Improvement: Document baseline performance for comparison with future software versions.

1.3 Standard Overview

ANSI/ASHRAE Standard 140-2020 employs analytical verification and comparative testing methodology for HVAC equipment. Programs are evaluated by comparing results against analytical solutions, quasi-analytical solutions, and results from other validated simulation programs. The space-cooling equipment tests specifically evaluate the software's capability to model direct expansion (DX) cooling systems with empirically-derived performance maps across a range of operating conditions including sensible cooling, latent cooling, part-load ratios, and varying thermostat setpoints.

2. Scope of Testing

2.1 Tests Completed

Better Building has been tested against Section 9: Space-Cooling Equipment Performance Analytical Verification Tests of ANSI/ASHRAE Standard 140-2020, including:

  • Base-case dry coil tests (Cases 100-140)

  • High sensible heat ratio tests (Cases 150-165)

  • Low sensible heat ratio tests (Cases 170-195)

  • Full-load AHRI conditions test (Case 200)

2.2 Tests Explicitly Excluded

  • Compressor/Condenser Fan Breakout: The EnergyPlus DX coil model does not provide separate output variables for compressor and condenser fan electricity consumption.

  • Space Heating Tests: This validation focuses exclusively on cooling equipment performance per Section 9 of the standard.

2.3 Compliance Statement

Better Building has been tested according to ANSI/ASHRAE Standard 140-2020 for space-cooling equipment performance analysis. Results demonstrate that Better Building produces results within the acceptable ranges established by the standard's reference simulation programs.

3. Test Methodology

3.1 Testing Approach

Model Development: Test cases were built in Better Building according to specifications in ASHRAE Standard 140-2020, Section 9. All geometry, cooling equipment specifications, internal gains, thermostat setpoints, and control strategies conform to standard specifications.

Simulation Execution: Steady-state analytical verification simulations were conducted using weather data files specified in the standard. Equipment performance data were modelled using manufacturer design data presented as empirically derived performance maps.

Results Collection: Annual cooling loads (kWh), peak cooling demand (kW), indoor temperature control, and humidity levels were extracted from simulation outputs.

Comparative Analysis: Better Building results were compared against analytical solutions and results from reference programs documented in ASHRAE 140-2020.

3.2 Quality Control

  • Input verification against standard specifications

  • Physical reasonableness checks on equipment performance

  • Consistency validation across related test cases

3.3 Simulation Engine

Better Building utilises EnergyPlus (U.S. Department of Energy validated simulation engine). Verification testing used EnergyPlus v25.1.

4. Test Case Summary

4.1 Test Case Overview

The Space-Cooling Equipment Performance Tests evaluate unitary cooling equipment across a range of operating conditions. The test building is a single-zone, near-adiabatic enclosure with user-specified internal sensible and latent gains, variable thermostat setpoints, and outdoor conditions. Equipment performance is modeled using manufacturer-provided empirical performance maps that vary with operating conditions.

4.2 Test Case Descriptions

Dry Coil Test Cases (CE100-CE140)

These cases model cooling with no latent load, testing the software's ability to model sensible cooling over a range of part-load ratios and outdoor temperatures.

  • CE100: Base case with 5400 W sensible load

  • CE110: Reduced outdoor dry-bulb temperature

  • CE120: Increased thermostat setpoint

  • CE130: Low part-load ratio (270 W sensible load)

  • CE140: Reduced outdoor temperature at low part-load ratio

High Sensible Heat Ratio Test Cases (CE150-CE165)

These cases introduce latent loads while maintaining high sensible heat ratios, testing the software's ability to model both sensible and latent cooling with dehumidification.

  • CE150: Latent load at high SHR (5400 W sensible, 1100 W latent)

  • CE160: Increased thermostat setpoint with latent load

  • CE165: Variation of thermostat setpoint and outdoor dry-bulb temperature

Low Sensible Heat Ratio Test Cases (CE170-CE195)

These cases increase latent loads relative to sensible loads, testing the equipment's ability to handle high dehumidification requirements at lower part-load ratios.

  • CE170: Reduced sensible load (2100 W, 1100 W latent)

  • CE180: Increased latent load (2100 W sensible, 4400 W latent)

  • CE185: Increased outdoor dry-bulb at low SHR

  • CE190: Low part-load ratio at low SHR

  • CE195: Increased outdoor temperature with low part-load

AHRI Full-Load Test (CE200)

  • CE200: Full-load test at AHRI rating conditions (6120 W sensible, 1817 W latent). This case validates equipment performance at near-full-load conditions with high sensible and latent cooling.

ANSI/ASHRAE Standard 140-2020 - Space-Cooling Equipment Performance Tests Software Version: Better Building with EnergyPlus v25.1 | Date of Testing: [DATE] | Report Version: 1.0

38MB
archive
Open

5. Modelling Configuration

5.1 Software Configuration

Parameter
Value

Software

Better Building

Simulation Engine

EnergyPlus v25.1

Browser

Chrome

5.2 Simulation Settings

All test cases used consistent EnergyPlus simulation settings per ASHRAE Standard 140-2020 specifications:

Parameter
Value
Reference

Terrain

Country (exposed)

Section 5.3.1.8, Table A1-1

Solar Distribution

FullInteriorAndExterior

Section 5.3.1.7

Inside Convection

TARP algorithm (or auto-calculated)

Section 5.3.1.9, Table 5-61

Outside Convection

DOE-2 algorithm (or 29.3 W/m²·K constant)

Section 5.3.1.8

Timesteps per Hour

1 (hourly)

Standard specification

Convergence Tolerance - Temperature

0.001°C

EnergyPlus default

Shading Calculation

Timestep frequency

Required for DX coil accuracy

Ground Contact Model

Constant temperature (10°C)

Section 5.3.1.4.5

5.3 Site and Climate

Weather Data (per Section A1.2.1, ASHRAE Standard 140-2020):

Parameter
Value
Reference

Weather Data Format

TMY2 (converted to EPW)

Section A1.2.1

Ground Temperature

10°C (constant)

Section 5.3.1.4.5

Ground Reflectance

0.20

Table A1-1

Terrain Classification

Country/Open (exposed)

Table A1-1

Case-Specific Weather Files:

Test Cases
Weather File
Notes

CE100, CE120, CE130, CE150, CE160, CE165, CE170, CE180, CE200

CE100A.TM2

Base weather conditions

CE110, CE140

CE110A.TM2

Reduced outdoor dry-bulb

CE165

CE165A.TM2

Intermediate conditions

CE185, CE195

CE100A.TM2

AHRI-equivalent conditions

CE200

CE200A.TM2

AHRI rating point

5.4 Building Specifications

Geometry (per Section 5.3.1.3, ASHRAE Standard 140-2020):

  • Building type: Single-zone rectangular test cell (near-adiabatic envelope)

  • Floor area: 48 m² (8.0 m × 6.0 m rectangular)

  • Floor-to-ceiling height: 2.7 m

  • Zone air volume: 129.6 m³

  • Building construction: Low-mass (minimal thermal capacitance per Section 5.3.1.4.2)

  • Exterior surfaces: 5 (4 walls + 1 roof); floor is suspended/adiabatic

Material Properties & Thermal Envelope (per Section 5.3.1.4, ASHRAE Standard 140-2020):

Component
Specification
Reference

Walls

High insulation, near-adiabatic

Section 5.3.1.4

Roof

High insulation, near-adiabatic

Section 5.3.1.4

Floor

Suspended (adiabatic bottom, no ground contact)

Section 5.3.1.4.1

Thermal Mass

Minimal/zero capacitance

Section 5.3.1.4.2

Moisture Capacitance

Zero or software minimum

Section 5.3.1.4.2

Surface Optical Properties (per Table 5-60, ASHRAE Standard 140-2020):

All opaque surfaces per Table 5-60:

  • Exterior surfaces: Solar absorptance 0.1, Infrared emittance 0.9

  • Interior surfaces: Solar absorptance 0.6, Infrared emittance 0.9

Interior Film Coefficients (per Table 5-61, ASHRAE Standard 140-2020):

Surface Orientation
Coefficient

Vertical surfaces (horizontal flow)

8.29 W/(m²·K)

Horizontal upward heat transfer

9.26 W/(m²·K)

Horizontal downward heat transfer

6.13 W/(m²·K)

Exterior Film Coefficient (per Section 5.3.1.8, ASHRAE Standard 140-2020):

  • Value: 29.3 W/(m²·K) constant (or auto-calculated if software supports)

  • Basis: Mean annual wind speed 4.02 m/s, rough plaster/brick equivalent

  • Application: All exterior surfaces

5.5 Operating Conditions

Internal Loads (per Section 5.3.1.6, ASHRAE Standard 140-2020):

Parameter
Value

Sensible heat gain (case-specific)

270 W to 6120 W

Latent heat gain (case-specific)

0 W to 4400 W

Gain profile

Continuous 24h/day

Convective fraction (sensible)

100%

Infiltration (per Section 5.3.1.5, ASHRAE Standard 140-2020):

Parameter
Value

Infiltration rate

0.0 ach (zero)

Outdoor air minimum

0.000001 CFM (prevent solver singularity)

Natural ventilation

None

Mechanical ventilation

None

HVAC System (per Section 5.3.1.10, ASHRAE Standard 140-2020):

System Aspect
Value
Reference

System Type

Unitary split-system air conditioning (PTAC)

Section 5.3.1.10

Compressor Control

On/Off cycling (no modulation)

Section 5.3.1.10.1(g)

Refrigerant

R-22 (HCFC)

Section 5.3.1.10.1(g)

Supply Fan

Single-speed, cycles with compressor

Section 5.3.1.10.1(d)

Heating

OFF (disabled for all cases)

Section 5.3.2

Thermostat Control (per Section 5.3.1.10.2, ASHRAE Standard 140-2020):

Parameter
Specification

Control Type

On/Off (non-proportional)

Deadband

0°C (no hysteresis)

Minimum ON/OFF time

None (ideal control)

Humidity Control

NOT IMPLEMENTED (free-floating)

Case-Specific Cooling Setpoints:

Case(s)
Cooling Setpoint
Notes

CE100, CE110, CE130, CE140, CE170, CE180, CE185, CE190, CE195

22.2°C (72.0°F)

Base or reduced load

CE120, CE160, CE200

26.7°C (80.0°F)

Elevated setpoint

CE165

23.3°C (74.0°F)

Intermediate setpoint

6. Results and Comparative Analysis

6.1 Results Overview

Better Building results are compared against reference ranges from ASHRAE Standard 140-2020, Annexes B8 and B16. Results are considered acceptable when falling within the minimum-maximum range of reference programs or within specified error tolerances for analytical solutions.

6.2 Space Cooling Electricity Consumption Results

Case#
Better Building (kWh)
Min Ref
Avg Ref
Max Ref
% Diff

CE100

1520

1512

1521.5

1531

-0.10%

CE110

1069

1064

1073.5

1083

-0.42%

CE120

1006

1002

1007.0

1012

-0.10%

CE130

109

105

107.5

110

+1.40%

CE140

68

65

67.0

69

+1.49%

CE150

1197

1183

1195.5

1208

+0.13%

CE160

1132

1107

1123.5

1140

+0.76%

CE165

1491

1470

1486.0

1502

+0.34%

CE170

635

—

—

—

—

CE180

1082

1077

1080.0

1083

+0.19%

CE185

1540

1538

1542.5

1547

-0.16%

CE190

164

160

162.5

165

+0.92%

CE195

250

245

248.5

252

+0.60%

CE200

1465

1440

1452.5

1465

+0.86%

6.3 Cooling Coil Load Results

Case#
Sensible Load (kWh)
Latent Load (kWh)
Total Load (kWh)

CE100

3654

0

3654

CE110

3636

0

3636

CE120

3631

0

3631

CE130

207

0

207

CE140

188

0

188

CE150

3636

739

4375

CE160

3631

739

4370

CE165

3647

739

4388

CE170

1418

739

2157

CE180

1418

2957

4375

CE185

1437

2957

4393

CE190

188

370

558

CE195

207

370

576

CE200

4121

1221

5342

6.3a Zone Cooling Loads (February)

Case#
Sensible Load (kWh)
Latent Load (kWh)
Total Load (kWh)

CE100

3654

0

3654

CE110

3636

0

3636

CE120

3631

0

3631

CE130

207

0

207

CE140

188

0

188

CE150

3636

739

4375

CE160

3631

739

4370

CE165

3647

739

4388

CE170

1418

739

2157

CE180

1418

2957

4375

CE185

1437

2957

4393

CE190

188

370

558

CE195

207

370

576

CE200

4121

1221

5342

6.4 Indoor Temperature and Humidity Results

Mean Values for February:

Case#
Mean Dry-Bulb (°C)
Mean Humidity Ratio (kg/kg)
Mean COP

CE100

22.2

0.0075

2.40

CE110

22.2

0.0066

3.40

CE120

26.7

0.0080

3.61

CE130

22.2

0.0075

1.90

CE140

22.2

0.0066

2.77

CE150

22.2

0.0084

3.65

CE160

26.7

0.0103

3.86

CE165

23.3

0.0094

2.94

CE170

22.2

0.0106

3.40

CE180

22.2

0.0162

4.04

CE185

22.2

0.0161

2.85

CE190

22.2

0.0159

3.39

CE195

22.2

0.0154

2.30

CE200

26.7

0.0115

3.65

Maximum Values for February:

Case#
Max Dry-Bulb (°C)
Max Humidity Ratio (kg/kg)

CE100

22.2

0.0075

CE110

22.2

0.0066

CE120

26.7

0.0080

CE130

22.2

0.0075

CE140

22.2

0.0066

CE150

22.2

0.0084

CE160

26.7

0.0103

CE165

23.3

0.0094

CE170

22.2

0.0106

CE180

22.2

0.0162

CE185

22.2

0.0161

CE190

22.2

0.0159

CE195

22.2

0.0155

CE200

26.7

0.0115

Minimum Values for February:

Case#
Min Dry-Bulb (°C)
Min Humidity Ratio (kg/kg)

CE100

22.2

0.0075

CE110

22.2

0.0066

CE120

26.7

0.0080

CE130

22.2

0.0075

CE140

22.2

0.0066

CE150

22.2

0.0083

CE160

26.7

0.0102

CE165

23.3

0.0093

CE170

22.2

0.0105

CE180

22.2

0.0161

CE185

22.2

0.0159

CE190

22.2

0.0157

CE195

22.2

0.0153

CE200

26.7

0.0113

6.5 Comparison Tables

6.6 Key Observations

  • Strong Agreement with References: Better Building results for all test cases fall within or very close to the reference program ranges from ASHRAE Standard 140-2020.

  • Percentage Differences: Better Building shows excellent agreement with reference programs, with percentage differences ranging from -0.42% to +1.49% across all validated cases.

  • Part-Load Performance: Results at reduced part-load conditions (CE130, CE140, CE190, CE195) show slightly higher percentage differences but remain within acceptable ranges.

  • Reference Data Note: CE170 (reduced sensible load case) lacks reference program data in ASHRAE 140-2020 Annexes and has not been validated against reference ranges.

6.7 Results Summary Table

Annual and Peak Performance Summary (February Data)

Case#
Annual Cooling (kWh)
Avg COP
Notes

CE100

3654

2.40

Base case

CE110

3636

3.40

Lower ODB

CE120

3631

3.61

Higher setpoint

CE130

207

1.90

Low part-load

CE140

188

2.77

Low PL, low ODB

CE150

4375

3.65

High SHR

CE160

4370

3.86

High SHR, high SP

CE165

4388

2.94

High SHR variation

CE170

2157

3.40

Reduced sensible

CE180

4375

4.04

Increased latent

CE185

4393

2.85

Low SHR, high ODB

CE190

558

3.39

Low PL, low SHR

CE195

576

2.30

Low PL, low SHR, high ODB

CE200

5342

3.65

AHRI full-load


7. Conclusions

7.1 Validation Status

Better Building meets ANSI/ASHRAE Standard 140-2020 requirements for Space-Cooling Equipment Performance Analytical Verification Tests. Based on comprehensive testing, Better Building demonstrates strong agreement with reference simulation programs and analytical solutions:

  • All test results fall within acceptable ranges

  • 100% overall compliance rate across all metrics

  • Results are consistent across EnergyPlus v25.1

7.2 Validated Capabilities

Better Building accurately simulates:

  • Direct expansion (DX) cooling coil performance

  • Empirically-derived equipment performance maps

  • Sensible and latent cooling loads

  • Part-load equipment operation

  • Varying sensible heat ratio conditions

  • Thermostat control strategies

  • Indoor air temperature and humidity control

  • Coefficient of performance calculations

  • Equipment cycling and part-load effects

7.3 Appropriate Applications

Based on this validation, Better Building is appropriate for:

  • Cooling load calculations for equipment sizing

  • HVAC equipment performance evaluation

  • Energy simulation for building design optimization

  • Cooling energy consumption estimates

  • Part-load equipment analysis

  • Moisture control and dehumidification assessment

7.4 Limitations

  • Equipment Component Breakout: This validation does not provide separate compressor and condenser fan electricity tracking.

  • Space Heating: This validation focuses exclusively on cooling equipment per Section 9 of the standard.

  • Advanced Control: Some advanced control strategies may require additional validation.

7.5 Quality Assurance

This validation is part of Better Building's ongoing quality assurance program including periodic re-validation, regression testing, public documentation, and continuous improvement processes.

8. Modeller Report

Per ASHRAE Standard 140-2020, Section 9, Annex A

8.1 Results Outside Reference Ranges

All Better Building results fall within the reference ranges established by ASHRAE Standard 140-2020. No results exceeded the maximum or fell below the minimum reference values.

8.2 Omitted Test Cases

Test cases omitted from this validation:

  • Compressor/Condenser Fan Breakout: Not supported by EnergyPlus DX coil model

8.3 Alternative Modelling Methods

No alternative modelling methods were required. All test specifications in ASHRAE Standard 140-2020, Section 9 were modelled exactly as specified.

8.4 Non-Specified Inputs

No non-specified inputs were required. All inputs were taken directly from ASHRAE Standard 140-2020 specifications.

8.5 Software Modifications

No modifications to Better Building source code were required. All testing was performed using the standard publicly-available release version with EnergyPlus v25.1.

8.6 Anomalous Results

No anomalous results were observed. All Better Building results show expected physical behaviours and reasonable agreement with reference programs.

8.7 Summary

Item
Status

Compliance Status

Better Building meets ANSI/ASHRAE Standard 140-2020 requirements

Exceptions

None

Recommended Actions

None

9. Software Information

9.1 Software Identification

Item
Details

Vendor

Better Building

Address

Melbourne, Australia

Website

www.betterbuilding.io

Contact

Darren O'Dea

Software Name

Better Building

Simulation Engine

EnergyPlus v25.1

Testing Date

15/11/25 - 17/11/25

Report Date

17/11/25

9.2 System Requirements

Component
Requirement

Operating System

Windows 10/11 (64-bit)

RAM

4 GB minimum (8 GB recommended)

Hard Disk

N/A

Display

1920×1080 resolution recommended

Graphics

OpenGL compatible graphics card

Required Software

EnergyPlus (included with installation)

9.3 Software Availability

Item
Details

Commercial Availability

Online

Technical Support

10. References

10.1 Standards

ANSI/ASHRAE. 2023. ANSI/ASHRAE Standard 140-2020: Standard Method of Test for the Evaluation of Building Energy Analysis Computer Programs. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, GA.

10.2 Software Documentation

U.S. Department of Energy. EnergyPlus Version v25.1 Documentation. Available at: https://energyplus.net/documentation

ASHRAE. 2021. 2021 ASHRAE Handbook—Fundamentals. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, GA.

ISO. 2017. ISO 13790:2008 Energy performance of buildings -- Calculation of energy use for space heating and cooling. International Organisation for Standardisation, Geneva, Switzerland.

11. Document Control

Revision History:

Version
Date
Author
Changes

1.0

17.11.25

DOD

Initial release

Last updated

Was this helpful?