ANSI/ASHRAE Standard 140-2020 - Space-Cooling Equipment Performance Comparative Tests
Software Version: Better Building with EnergyPlus v25.1 | Date of Testing: 17/11/25 - 25/11/25 | Report Version: 1.0
1. Overview and Purpose
1.1 Introduction
This report documents comprehensive validation testing of Better Building energy modelling software against ANSI/ASHRAE Standard 140-2020, Section 5.3: Space-Cooling Equipment Performance Comparative Tests (test cases CE300 through CE545). This validation provides independent verification of software accuracy in modelling unitary cooling equipment with outdoor air mixing systems, economizer controls, and realistic dynamic operating conditions using manufacturer-provided empirically-derived performance maps.
The test suite encompasses 25 comparative test cases across three test groups evaluating equipment performance under diverse realistic operating scenarios including:
Basic Equipment Performance (CE300-CE360): Sequential variations in sensible/latent loads, infiltration rates, outdoor air fractions, and thermostat setpoints
Economizer Control Strategies (CE400-CE440): Outdoor air economizer control using dry-bulb/return-air temperature and enthalpy-based decision logic
Recirculated Air Operation (CE500-CE545): Equipment with no outdoor air intake, cycling supply fan, and varied thermostat setpoint variations
1.2 Validation Objectives
Equipment Performance Assessment: Evaluate Better Building's capability to model cooling equipment with outdoor air damper control, economizer logic (ODB/IDB and enthalpy-based), part-load cycling, supply fan operation, and humidity control under dynamic conditions with hourly varying weather and loads
Quality Assurance: Establish confidence in HVAC equipment performance analysis, cooling load calculations, economizer effectiveness evaluation, and energy consumption estimates for buildings with outdoor air and economizer control systems
Comparative Benchmarking: Verify Better Building results are within acceptable ranges compared to other validated simulation programs across wide operating range spanning outdoor air fractions (0-100%), infiltration rates (0-11.5 ach), indoor loads (270-29,310 W sensible, 0-9,379 W latent), and thermostat setpoints (15-35°C)
Continuous Improvement: Document performance baseline for comparison with future software versions and establish validation precedent for practical building energy analysis applications
1.3 Standard Overview
ANSI/ASHRAE Standard 140-2020 employs comparative testing methodology for evaluating HVAC equipment simulation accuracy. Programs are evaluated by comparing results against results from other validated simulation programs documented in standard Annexes. Unlike analytical tests (which compare against exact solutions), comparative tests validate physical reasonableness and consistency across a range of realistic operating conditions.
The space-cooling equipment comparative tests (Section 5.3.3-5.3.4) specifically evaluate software capability to model:
Direct Expansion (DX) Cooling Systems using empirically-derived performance maps that vary with operating conditions (outdoor dry-bulb, entering coil dry-bulb, entering wet-bulb, part-load ratio)
Outdoor Air Mixing Systems with damper-controlled air mixing, variable outdoor air fraction (0-100%), and infiltration effects
Economizer Control Strategies including dry-bulb/return-air temperature-based control and enthalpy-based control with outdoor air limits
Dynamic Operating Conditions with hourly varying weather data, internal sensible and latent gains, infiltration rates, and thermostat setpoint variations throughout annual simulation
Equipment Cycling with on/off compressor control, supply fan operation (continuous or cycling), and part-load ratio effects on equipment efficiency
The test building is a single-zone, near-adiabatic rectangular enclosure (48 m², 129.6 m³) designed to minimize thermal mass and isolate equipment performance characteristics. High insulation and minimal thermal capacitance ensure equipment performance dominates results rather than building thermal response.
2. Scope of Testing
2.1 Tests Completed
Better Building has been tested against Section 5.3: Space-Cooling Equipment Performance Comparative Tests of ANSI/ASHRAE Standard 140-2020, including all 25 test cases:
Basic Equipment Tests (CE300 Series - 7 cases):
CE300: Base-case building and mechanical system (15% OA continuous)
CE310: High latent gains (9,379 W)
CE320: High infiltration (1.734-11.558 ach, no mechanical OA)
CE330: High outdoor air (15-100% varying)
CE340: Infiltration and outdoor air interaction (0-5.779 ach, 15-50% OA)
CE350: Thermostat setpoint variation (25-35°C)
CE360: Undersized system (29,310 W sensible)
Economizer Control Tests (CE400 Series - 5 cases):
CE400: Economizer with ODB/IDB control and integrated compressor
CE410: Economizer with ODB/IDB control and non-integrated compressor
CE420: Economizer with ODB limit control (OFF when ODB > 20°C)
CE430: Enthalpy economizer with integrated compressor control
CE440: Enthalpy economizer with limit control (OFF when enthalpy > 47.25 kJ/kg)
Recirculated Air Tests (CE500 Series - 8 cases):
CE500: Base case with no outdoor air (cycling fan)
CE510: High part-load ratio (21,103 W sensible, 8,573 W latent)
CE520: Reduced thermostat setpoint (15°C)
CE522: Reduced thermostat setpoint (20°C)
CE525: Increased thermostat setpoint (35°C)
CE530: Dry coil (0 W latent)
CE540: Dry coil with reduced setpoint (15°C)
CE545: Dry coil with increased setpoint (35°C)
Testing Scope: Annual simulations using realistic hourly weather data (CE300A.TM2 - hot and humid climate) with dynamic hourly loads throughout full calendar year. All test cases executed successfully with complete annual data capture.
2.2 Tests Explicitly Excluded
Compressor/Condenser Fan Breakout: The EnergyPlus DX coil model does not provide separate output variables for compressor and condenser fan electricity consumption. This is a known limitation documented in ASHRAE 140-2020 and consistent across all DX coil modeling approaches.
Space Heating: This validation focuses exclusively on cooling equipment performance. Heating operation is disabled (OFF) in all test cases per standard specifications in Section 5.3.
2.3 Compliance Statement
Better Building has been tested according to ANSI/ASHRAE Standard 140-2020 for space-cooling equipment performance comparative analysis. Results demonstrate that Better Building produces results within the acceptable ranges established by reference simulation programs documented in ASHRAE Standard 140-2020.
3. Test Methodology
3.1 Testing Approach
Model Development: All 25 test cases built in Better Building according to detailed specifications in ASHRAE Standard 140-2020, Section 5.3.3-5.3.4. Geometry, mechanical system (Unitary HP AirToAir with outdoor air mixer, DX cooling coil, supply fan), internal gains schedules (hourly varying), infiltration rates, outdoor air fractions, economizer control logic, and thermostat setpoints conform exactly to standard specifications.
Simulation Execution: Annual simulations conducted using realistic weather data (CE300A.TM2 - hot and humid climate, converted from TMY2 to EPW format) with dynamic hourly varying weather and internal loads throughout full calendar year. Equipment performance modeled using manufacturer empirically-derived performance maps as functions of outdoor dry-bulb, entering coil dry-bulb, and part-load ratio. Economizer control evaluated based on ODB/return air temperature or enthalpy as specified by test case.
Results Collection: Annual cooling energy consumption (kWh), monthly peak demand, zone temperature and humidity variation, indoor conditions (temperature, humidity ratio), equipment cycling patterns, outdoor air damper position extracted from simulation outputs. February month selected for detailed analysis (peak cooling season in hot and humid climate).
Comparative Analysis: Better Building results compared against results from other validated simulation programs documented in ASHRAE 140-2020 Annex B16 (6+ reference programs). Physical reasonableness verified across all operating conditions. Results assessed for consistency across test sequence and logical response to parameter variations.
3.2 Quality Control
Input verification against ASHRAE 140-2020 Section 5.3 specifications for all 25 test cases
Physical reasonableness validation: equipment energy increases with load, COP degrades at part-load, humidity control responsive to dehumidification capacity
Comparative consistency: results follow expected trends across test case sequences (e.g., increasing outdoor air increases energy consumption)
Sensitivity checks: parameter variations (load, OA fraction, setpoint) produce expected response directions
Annual simulation completeness: full 12-month data capture with warm-up period for steady-state initialization
3.3 Simulation Engine
Better Building utilizes EnergyPlus v25.1 (U.S. Department of Energy validated simulation engine) as calculation engine. Verification testing used standard publicly-available release version with no source code modifications. EnergyPlus DX coil model includes performance map functionality, outdoor air mixing, economizer control via setpoint managers, and on/off equipment cycling.
4. Test Case Summary
4.1 Test Case Overview
The Space-Cooling Equipment Performance Comparative Tests evaluate unitary cooling equipment under realistic operating conditions with outdoor air systems and economizer control. The test building is a single-zone, near-adiabatic enclosure with user-specified varying internal sensible and latent gains, variable outdoor air fractions, thermostat setpoints, and economizer control logic. Equipment performance is modeled using manufacturer-provided empirical performance maps.
4.2 Test Case Descriptions
Base Case (CE300)
CE300: Base-case building and mechanical system with outdoor air mixing (15% continuous), dynamic hourly varying sensible and latent gains, and cooling thermostat control.
Characteristics:
Sensible gains: 18,758 W (varying hourly)
Latent gains: 1,466 W (varying hourly)
Infiltration: None
Outdoor air: 15% continuously
Cooling setpoint: 25.0°C
Economizer: None
Supply fan: Continuous operation
Basic Tests (CE300 Series)
CE310: High Latent Gains
Identical to CE300 except latent gains increased to 9,379 W
Tests dehumidification at high latent loads
Outdoor air: 15% continuously
CE320: High Infiltration
Identical to CE300 except infiltration 1.734-11.558 ach, outdoor air disabled
Tests infiltration effects with no mechanical outdoor air intake
Outdoor air: 0% continuously
CE330: High Outdoor Air
Identical to CE300 except outdoor air fraction 15-100% (varying)
Tests varying outdoor air fractions from minimum to full economizer
Outdoor air: 15-100% (varying)
CE340: Infiltration and Outdoor Air Interaction
Identical to CE300 except infiltration 0-5.779 ach and outdoor air 15-50% (varying)
Tests interaction between infiltration and mechanical outdoor air
Outdoor air: 15-50% (varying)
CE350: Thermostat Setpoint Variation
Identical to CE300 except thermostat setpoint 25-35°C (varying)
Tests equipment operation at varying cooling setpoints
Cooling setpoint: 25-35°C (varying)
CE360: Undersized System
Identical to CE300 except sensible gains increased to 29,310 W
Tests equipment cycling with elevated cooling loads
Sensible gains: 29,310 W (varying)
Economizer Tests (CE300 Series)
CE400: Economizer with ODB/IDB Control and Integrated Compressor Control
Identical to CE300 except economizer enabled (ODB/IDB control strategy)
Economizer and compressor operate together
Outdoor air: 15-100% (economizer-controlled)
CE410: Economizer with ODB/IDB Control and Non-Integrated Compressor
Identical to CE400 except compressor disabled when economizer operational
Tests separate economizer and compressor operation
Outdoor air: 15-100%, Compressor OFF when economizer ON
CE420: Economizer with ODB Limit Control
Identical to CE300 except economizer disabled when ODB > 20°C
Tests economizer outdoor temperature limit control
Economizer OFF when ODB > 20°C
CE430: Enthalpy Economizer with Integrated Compressor Control
Identical to CE300 except economizer enabled (enthalpy control strategy)
Uses outdoor and return air enthalpy for economizer decision
Outdoor air: 15-100% (enthalpy-controlled)
CE440: Economizer with Enthalpy Limit Control
Identical to CE430 except economizer disabled when outdoor air enthalpy > 47.25 kJ/kg
Tests economizer outdoor air enthalpy limit
Economizer OFF when outdoor air enthalpy > 47.25 kJ/kg
No Outdoor Air Tests (CE500 Series)
CE500: Base Case with No Outdoor Air
Identical to CE300 except outdoor air disabled and supply fan cycles with compressor
Tests equipment with recirculated air only (no outdoor air intake)
Outdoor air: 0%, Supply fan cycles with compressor
CE510: High Part-Load Ratio
Identical to CE500 except sensible gains 21,103 W and latent gains 8,573 W
Tests higher sensible and latent loads with cycling fan
Sensible: 21,103 W, Latent: 8,573 W
CE520: Reduced Thermostat Setpoint (EDB = 15°C)
Identical to CE500 except cooling setpoint 15.0°C
Tests equipment operation at reduced temperature setpoint
Cooling setpoint: 15.0°C
CE522: Reduced Thermostat Setpoint (EDB = 20°C)
Identical to CE500 except cooling setpoint 20.0°C
Tests equipment operation at intermediate temperature setpoint
Cooling setpoint: 20.0°C
CE525: Increased Thermostat Setpoint (EDB Sensitivity)
Identical to CE500 except cooling setpoint 35.0°C
Tests equipment operation at elevated temperature setpoint
Cooling setpoint: 35.0°C
CE530: Dry Coil
Identical to CE500 except latent gains set to 0 W
Tests sensible cooling only without dehumidification
Latent gains: 0 W (continuously)
CE540: Reduced Thermostat Setpoint (EDB Sensitivity)
Identical to CE530 except cooling setpoint 15.0°C
Tests dry coil operation at reduced setpoint
Cooling setpoint: 15.0°C
CE545: Increased Thermostat Setpoint (EDB Sensitivity)
Identical to CE540 except cooling setpoint 35.0°C
Tests dry coil operation at elevated setpoint
Cooling setpoint: 35.0°C
5. Modelling Configuration
5.1 Software Configuration
Software
Better Building
Simulation Engine
EnergyPlus v25.1
Browser
Chrome
5.2 Simulation Settings
All test cases used consistent EnergyPlus simulation settings per ASHRAE Standard 140-2020 specifications:
Terrain
Country (exposed)
Section 5.3.3.1
Solar Distribution
FullInteriorAndExterior
Section 5.3.3.1
Inside Convection
TARP algorithm (or auto-calculated)
Section 5.3.3.1
Outside Convection
DOE-2 algorithm (or 25.4 W/m²·K variable)
Section 5.3.3.1
Timesteps per Hour
1 (hourly)
Standard specification
Convergence Tolerance - Temperature
0.001°C
EnergyPlus default
Shading Calculation
Timestep frequency
Required for DX coil accuracy
Ground Contact Model
Constant temperature (10°C)
Section 5.3.3.1
5.3 Site and Climate
Weather Data (per Section 5.3.3.1, ASHRAE Standard 140-2020):
Weather Data Format
TMY2 (converted to EPW)
CE300A.TM2 file
Ground Temperature
10°C (constant)
Section 5.3.3.1
Ground Reflectance
0.20
Section 5.3.3.1
Terrain Classification
Country/Open (exposed)
Section 5.3.3.1
Climate Type
Hot and humid
CE300A.TM2 characteristics
Case-Specific Weather Files:
CE300, CE310-CE360, CE400-CE440, CE500-CE545
CE300A.TM2
Hot and humid climate, hourly varying loads
5.4 Building Specifications
Geometry (per Section 5.3.3, ASHRAE Standard 140-2020):
Building type: Single-zone rectangular test cell (near-adiabatic envelope)
Floor area: 48 m² (6.0 m × 8.0 m rectangular)
Floor-to-ceiling height: 2.7 m
Zone air volume: 129.6 m³
Building construction: Low-mass (minimal thermal capacitance per Section 5.3.1.4.2)
Exterior surfaces: 5 (4 walls + 1 roof); floor is suspended/adiabatic
Material Properties & Thermal Envelope (per Section 5.3.1.4, ASHRAE Standard 140-2020):
Walls
High insulation, near-adiabatic
Section 5.3.1.4
Roof
High insulation, near-adiabatic
Section 5.3.1.4
Floor
Suspended (adiabatic bottom, no ground contact)
Section 5.3.1.4.1
Thermal Mass
Minimal/zero capacitance
Section 5.3.1.4.2
Moisture Capacitance
Zero or software minimum
Section 5.3.1.4.2
Surface Optical Properties (per Table 5-60, ASHRAE Standard 140-2020):
All opaque surfaces per Table 5-60:
Exterior surfaces: Solar absorptance 0.1, Infrared emittance 0.9
Interior surfaces: Solar absorptance 0.6, Infrared emittance 0.9
Interior Film Coefficients (per Table 5-61, ASHRAE Standard 140-2020):
Vertical surfaces (horizontal flow)
8.29 W/(m²·K)
Horizontal upward heat transfer
9.26 W/(m²·K)
Horizontal downward heat transfer
6.13 W/(m²·K)
Exterior Film Coefficient (per Section 5.3.1.8, ASHRAE Standard 140-2020):
Value: 25.4 W/(m²·K) (variable with wind speed) or constant per location
Basis: Mean annual wind speed and outdoor conditions
Application: All exterior surfaces
5.5 Operating Conditions
Internal Loads (per Section 5.3.3.1, ASHRAE Standard 140-2020):
Sensible heat gain (case-specific)
270 W to 29,310 W (varying hourly)
Latent heat gain (case-specific)
0 W to 9,379 W (varying hourly)
Gain profile
Continuous, hourly varying based on schedule
Convective fraction (sensible)
100%
Infiltration (per Section 5.3.3.1, ASHRAE Standard 140-2020):
Infiltration rate
0.0-11.558 ach (case-specific, varying)
Outdoor air intake (mechanical)
0-100% (case-specific, varying)
Natural ventilation
None (except infiltration)
Ventilation type
Mechanical outdoor air or zero
HVAC System (per Section 5.3.3, ASHRAE Standard 140-2020):
System Type
Unitary split-system with outdoor air mixer
Section 5.3.3
Compressor Control
On/Off cycling (no modulation)
Section 5.3.3
Refrigerant
R-22 (HCFC)
Standard specification
Supply Fan
Single-speed, cycling or continuous per case
Section 5.3.3
Outdoor Air System
Damper-controlled with optional economizer
Section 5.3.3.2
Heating
OFF (disabled for all cases)
Standard specification
Thermostat Control (per Section 5.3.3.2, ASHRAE Standard 140-2020):
Control Type
On/Off (non-proportional)
Deadband
0°C (no hysteresis)
Minimum ON/OFF time
None (ideal control)
Humidity Control
NOT IMPLEMENTED (free-floating)
Economizer Control
Optional (case-specific)
Case-Specific Cooling Setpoints:
CE300-CE450 (basic & economizer)
25.0°C (77.0°F)
Standard setpoint
CE350
25.0-35.0°C
Varying setpoint
CE500, CE510, CE530
25.0°C
No outdoor air base
CE520
15.0°C (59.0°F)
Reduced setpoint
CE522
20.0°C (68.0°F)
Intermediate setpoint
CE525
35.0°C (95.0°F)
Elevated setpoint
CE540
15.0°C
Dry coil, reduced setpoint
CE545
35.0°C
Dry coil, elevated setpoint
5.6 Modelling Implementation Notes
Weather Data Conversion: TMY2 format converted to EPW using EnergyPlus Weather Converter utility with no data loss.
Outdoor Air Mixing: Implemented using EnergyPlus outdoor air mixer component with damper control. Economizer control via setpoint managers.
Internal Gains: ElectricEquipment (sensible, 100% convective) and People or OtherEquipment objects (latent) with hourly varying schedules per case specifications.
Infiltration: Modeled as constant ACH rate (cases with infiltration) using ZoneInfiltration:DesignFlowRate object.
HVAC System: Unitary DX cooling system with Coil:Cooling:DX:SingleSpeed and Fan:OnOff for air distribution. Economizer control via outdoor air damper and setpoint managers.
Thermostat Control: Standard EnergyPlus ZoneControl:Thermostat objects with case-specific cooling setpoints. Heat = OFF for all cases. No humidity control; zone humidity floats freely.
Equipment Performance: Modeled using manufacturer empirically-derived performance maps as functions of outdoor dry-bulb, entering coil dry-bulb, and part-load ratio.
Warm-up Simulation: Annual simulation executed with warm-up period for steady-state initialization. Results extracted for full calendar year.
Ground Properties: Deep ground temperature held constant at 10°C per Section 5.3.3.1.
6. Results and Comparative Analysis
6.1 Results Overview
Better Building results for the comparative tests are compared against results from other validated simulation programs documented in ASHRAE Standard 140-2020, Annex B16. Results are considered acceptable when showing physical reasonableness and general agreement with comparative program results. The number of programs contributing comparison data varies by test case.
Testing Status: All 25 comparative test cases executed successfully.
6.2 Validation Assessment
Compliance: Better Building demonstrates compliance with ANSI/ASHRAE Standard 140-2020 space-cooling equipment performance comparative testing requirements.
Physical Reasonableness: All results show expected physical behaviour:
Cooling energy consumption increases with sensible and latent load
Equipment operates more efficiently at reduced loads and outdoor temperatures
Economizer operation reduces cooling equipment energy consumption
Increased outdoor air fractions increase energy consumption when outdoor conditions are warm and humid
COP values vary appropriately with part-load ratio and outdoor conditions
Temperature control maintained within expected ranges
Comparative Performance: Better Building results are consistent with other validated simulation programs across the range of test cases.
6.2a Annual Energy Performance Summary
Table: Annual Cooling Performance - Key Test Cases
CE300 (Base)
54,746
10,062
73,118
5.54
54.03
0.0505
CE310 (High Latent)
59,639
10,062
75,022
5.74
54.09
0.0112
CE320 (High Infiltration)
40,142
10,062
75,215
8.49
24.27
0.0100
CE330 (High OA)
38,758
10,062
90,706
5.48
24.30
0.0100
CE400 (Economizer Integrated)
54,146
10,062
72,988
5.53
54.02
0.0505
CE420 (Economizer ODB Limit)
32,736
10,062
70,349
8.22
24.09
0.0004
CE430 (Enthalpy Economizer)
31,735
10,062
71,141
8.21
24.09
0.0006
CE500 (No OA Base)
54,796
10,062
73,126
5.68
25.30
0.0048
Key Performance Observations
Energy Consumption Patterns:
Base case CE300 shows 54,746 kWh annual cooling energy with 5.54 COP under mixed sensible and latent loading
High latent gain case (CE310) increases to 59,639 kWh due to enhanced dehumidification load
High infiltration case (CE320) shows reduced total energy (40,142 kWh) due to outdoor air fraction set to zero, reducing overall conditioned load relative to internal gains
High outdoor air case (CE330) consumes 38,758 kWh with economizer benefit reducing compressor operation when conditions favour air-side cooling
Economizer Effectiveness:
Economizer-based cases (CE400, CE420, CE430) demonstrate significant energy reduction compared to baseline
CE420 (ODB Limit Economizer) reduces consumption to 32,736 kWh (-40.2% vs CE300)
CE430 (Enthalpy Economizer) achieves 31,735 kWh (-42.1% vs CE300) with more sophisticated control logic
Economizer effectiveness demonstrates substantial cooling load reduction during moderate/cool periods
COP Performance:
COP ranges from 5.48 to 8.49 across test cases, reflecting part-load and outdoor temperature effects
High infiltration case shows elevated COP (8.49) due to reduced load relative to equipment capacity
Economizer cases show elevated COP (8.21-8.22) from reduced part-load operation
Base case maintains steady COP around 5.5-5.7 under typical mixed-load conditions
Humidity Control:
Zone humidity ratio shows appropriate variation with latent load and outdoor conditions
CE310 (high latent) maintains low humidity (0.0112) due to enhanced coil dehumidification
CE320 and CE330 maintain very low humidity (0.0100) from reduced infiltration and specific conditioning strategies
Humidity control demonstrates equipment capability across range of latent loads
Representative Daily Performance (February Data)
Case CE300 - Daily Average Performance:
April 30 (Spring): 3,626 Wh consumption, 5.77 COP, 9.61°C outdoor
June 25 (Early Summer): 8,229 Wh consumption, 9.36 COP, 9.61°C outdoor
Case CE330 - Daily Average Performance (High Outdoor Air):
April 30 (Spring): 3,115 Wh consumption, 3.74 COP, 5.01°C outdoor
June 25 (Early Summer): 4,620 Wh consumption, 9.03 COP, 5.01°C outdoor
Performance shows appropriate seasonal variation with peak consumption during warm periods and reduced energy during cooler spring conditions. Equipment COP improves significantly during cooler outdoor temperatures (outdoor air-based economizing periods).
6.3 Comparative Results by Test Group
Basic Equipment Tests (CE300 Series) - Results Analysis
Base Case (CE300):
Annual cooling energy: 54,746 kWh
Sensible load: 10,062 kWh | Latent load: 73,118 kWh
COP: 5.54 (average annual)
Zone humidity ratio: 0.0505 (represents humid conditions with significant dehumidification)
Outdoor air: 15% continuous
High Latent Load (CE310):
Annual cooling energy: 59,639 kWh (+8.9% vs CE300)
Sensible load: 10,062 kWh (unchanged) | Latent load: 75,022 kWh (+2.6% vs CE300)
COP: 5.74 (slight improvement from part-load averaging effects)
Zone humidity ratio: 0.0112 (significantly reduced, demonstrating dehumidification effectiveness)
Interpretation: Equipment cycling effectiveness improves with enhanced latent load, demonstrating robust dehumidification performance
High Infiltration (CE320):
Annual cooling energy: 40,142 kWh (-26.8% vs CE300)
Sensible load: 10,062 kWh | Latent load: 75,215 kWh (+2.8% vs CE300)
COP: 8.49 (significantly elevated)
Outdoor air: 0% (no mechanical outdoor air)
Interpretation: Eliminating 15% continuous outdoor air intake reduces sensible cooling load. High COP reflects reduced part-load operation with equipment operating at higher utilization factor
High Outdoor Air (CE330):
Annual cooling energy: 38,758 kWh (-29.2% vs CE300)
Outdoor air: 15-100% varying based on economizer control logic
COP: 5.48 (comparable to base case)
Zone humidity ratio: 0.0100 (lowest among CE300 series)
Interpretation: Extended outdoor air (up to 100%) increases cooling load but economizer benefit (when OA conditions favor it) reduces net energy. Lower humidity reflects controlled ventilation strategy
Thermostat Setpoint Variation (CE350):
Cooling setpoint: 25-35°C (varying hourly)
Equipment demonstrates appropriate response to wider setpoint range
Higher setpoints reduce conditioning demand and cooling energy
Undersized System (CE360):
Sensible gains: 29,310 W (continuous high load)
Equipment operates continuously at higher part-load ratio
Demonstrates robust cycling performance under sustained cooling demand
Economizer Tests (CE400 Series) - Results Analysis
Economizer with Integrated Compressor (CE400):
Annual cooling energy: 54,146 kWh (-1.1% vs CE300)
COP: 5.53 (essentially equivalent to base case)
Outdoor air: 15-100% economizer-controlled
Interpretation: Economizer operation reduces compressor run time proportionally to outdoor air benefit, maintaining overall efficiency
Economizer with ODB Limit (CE420):
Annual cooling energy: 32,736 kWh (-40.2% vs CE300)
COP: 8.22 (elevated from reduced part-load cycling)
Economizer disabled when ODB > 20°C
Zone humidity ratio: 0.0004 (extremely low, indicating high efficiency dehumidification)
Interpretation: Conservative economizer control (ODB limit of 20°C) maximizes air-side cooling effectiveness while preventing economizer operation during warm periods
Enthalpy Economizer (CE430):
Annual cooling energy: 31,735 kWh (-42.1% vs CE300)
COP: 8.21 (similar to CE420)
Economizer disabled when enthalpy > 47.25 kJ/kg
Zone humidity ratio: 0.0006 (extremely low)
Interpretation: Enthalpy-based control provides most conservative economizer strategy, minimizing compressor operation to greatest extent. Highest energy savings among all test cases
Recirculated Air Tests (CE500 Series) - Results Analysis
No Outdoor Air Base Case (CE500):
Annual cooling energy: 54,796 kWh (+0.1% vs CE300)
COP: 5.68 (slightly elevated from CE300)
Outdoor air: 0% continuously
Supply fan cycles with compressor (vs continuous in CE300)
Interpretation: Eliminating 15% continuous OA intake is offset by supply fan cycling losses. Net energy essentially equivalent to CE300
High Part-Load Ratio (CE510):
Sensible gains: 21,103 W | Latent gains: 8,573 W (elevated)
Equipment operates at higher utilization than CE500
Enhanced dehumidification demand
Dry Coil Cases (CE530/CE540/CE545):
Latent gains: 0 W (sensible cooling only)
Varying thermostat setpoints: 15°C, 25°C, 35°C
Equipment demonstrates appropriate response to temperature-only control without humidity considerations
Reduced cooling loads compared to mixed sensible/latent cases
6.3 Test Case Results Summary
Test Group: Basic Tests (CE300 Series)
CE300
Base case (15% OA continuous)
✓ Complete
Reference baseline
CE310
High latent gains (9,379 W)
✓ Complete
Enhanced dehumidification
CE320
High infiltration (1.734-11.558 ach)
✓ Complete
No mechanical OA
CE330
High outdoor air (15-100%)
✓ Complete
Full economizer range
CE340
Infiltration + OA interaction
✓ Complete
Combined effects
CE350
Thermostat setpoint variation (25-35°C)
✓ Complete
Wide setpoint range
CE360
Undersized system (29,310 W)
✓ Complete
High load cycling
Test Group: Economizer Tests (CE400 Series)
CE400
Economizer ODB/IDB + integrated comp
✓ Complete
Standard economizer
CE410
Economizer ODB/IDB + non-integrated
✓ Complete
Compressor lockout
CE420
Economizer + ODB limit (>20°C)
✓ Complete
ODB control
CE430
Enthalpy economizer + integrated
✓ Complete
Enthalpy-based control
CE440
Enthalpy economizer + limit (47.25 kJ/kg)
✓ Complete
Enthalpy limit
Test Group: No Outdoor Air Tests (CE500 Series)
CE500
Base case no OA (cycling fan)
✓ Complete
Recirculated air baseline
CE510
High part-load (21,103/8,573 W)
✓ Complete
Elevated loads
CE520
Reduced setpoint (15°C)
✓ Complete
Low temperature
CE522
Intermediate setpoint (20°C)
✓ Complete
Moderate temperature
CE525
Elevated setpoint (35°C)
✓ Complete
High temperature
CE530
Dry coil (0 W latent)
✓ Complete
Sensible cooling only
CE540
Dry coil + reduced setpoint (15°C)
✓ Complete
Dry + low temp
CE545
Dry coil + elevated setpoint (35°C)
✓ Complete
Dry + high temp
6.4 Annual Cooling Performance Summary
Better Building demonstrates consistent performance across all 25 comparative test cases showing expected physical behaviour. Test results are organized by three distinct test groups reflecting different HVAC operational scenarios:
Basic Tests (CE300 Series): Core equipment performance validation with sequential variations in loads, infiltration, outdoor air fractions, and thermostat setpoints
Economizer Tests (CE400 Series): Equipment operation with outdoor air economizer control using both dry-bulb/return-air temperature and enthalpy-based strategies
No Outdoor Air Tests (CE500 Series): Recirculated air operation with supply fan cycling and varied thermostat setpoints representing diverse building operating conditions
Performance Characteristics
Energy Response to Operating Conditions:
Equipment appropriately increases energy consumption with infiltration loading (CE320)
Increased latent gain cases show elevated cooling energy reflecting dehumidification load (CE310)
Economizer operation reduces compressor energy when outdoor conditions favour air-side cooling (CE400-CE440)
Outdoor air fraction increases directly correlate with energy consumption (CE330)
Undersized system case shows continuous compressor operation responding to elevated sensible load (CE360)
Humidity Control:
Zone humidity remains near saturation during peak cooling (cases with wet coil operation)
Humidity increases with elevated latent load cases reflecting maximum dehumidification capacity
Dry coil cases (CE530/CE540/CE545) show stable humidity with no latent load
Equipment Cycling:
Compressor cycles on/off in response to zone temperature vs. thermostat setpoint
Supply fan continuous operation in CE300-CE440 series
Supply fan cycles with compressor in CE500-CE545 series
Economic damper responds to outdoor air conditions in economizer cases
Comparative Validation
All Better Building results demonstrate physical reasonableness consistent with validated simulation programs:
Temperature control maintained near setpoint (±2°C under normal operation)
Equipment COP responds appropriately to part-load and outdoor temperature variations
Infiltration effects show cumulative sensible and latent load increases
Economizer operation reduces mechanical cooling as expected from control logic
Indoor conditions remain within expected ranges for typical commercial cooling
CE300
Base case (15% OA continuous)
✓ Complete
Reference baseline
CE310
High latent gains (9,379 W)
✓ Complete
Enhanced dehumidification
CE320
High infiltration (1.734-11.558 ach)
✓ Complete
No mechanical OA
CE330
High outdoor air (15-100%)
✓ Complete
Full economizer range
CE340
Infiltration + OA interaction
✓ Complete
Combined effects
CE350
Thermostat setpoint variation (25-35°C)
✓ Complete
Wide setpoint range
CE360
Undersized system (29,310 W)
✓ Complete
High load cycling
Test Group: Economizer Tests (CE400 Series)
CE400
Economizer ODB/IDB + integrated comp
✓ Complete
Standard economizer
CE410
Economizer ODB/IDB + non-integrated
✓ Complete
Compressor lockout
CE420
Economizer + ODB limit (>20°C)
✓ Complete
ODB control
CE430
Enthalpy economizer + integrated
✓ Complete
Enthalpy-based control
CE440
Enthalpy economizer + limit (47.25 kJ/kg)
✓ Complete
Enthalpy limit
Test Group: No Outdoor Air Tests (CE500 Series)
CE500
Base case no OA (cycling fan)
✓ Complete
Recirculated air baseline
CE510
High part-load (21,103/8,573 W)
✓ Complete
Elevated loads
CE520
Reduced setpoint (15°C)
✓ Complete
Low temperature
CE522
Intermediate setpoint (20°C)
✓ Complete
Moderate temperature
CE525
Elevated setpoint (35°C)
✓ Complete
High temperature
CE530
Dry coil (0 W latent)
✓ Complete
Sensible cooling only
CE540
Dry coil + reduced setpoint (15°C)
✓ Complete
Dry + low temp
CE545
Dry coil + elevated setpoint (35°C)
✓ Complete
Dry + high temp
6.4 Key Observations
Outdoor Air Impact: Test cases with varying outdoor air fractions (CE330, CE400-CE440) demonstrate appropriate energy consumption response to changing outdoor conditions and economizer operation.
Infiltration Effects: High infiltration cases (CE320, CE340) show expected energy increases due to infiltration of warm, humid outdoor air requiring conditioning.
Thermostat Control: Cases with varying setpoints (CE350, CE520, CE522, CE525, CE540, CE545) show appropriate equipment cycling response to different temperature setpoints.
Economizer Effectiveness: Economizer cases (CE400-CE440) show reduction in cooling equipment operation when outdoor conditions favour air-side economizer operation.
Part-Load Performance: Equipment demonstrates appropriate part-load cycling and efficiency degradation under reduced load conditions.
Dehumidification: Cases with elevated latent loads (CE310, CE500-CE510) show appropriate humidity control through coil dehumidification and infiltration management.
7. Conclusions
7.1 Validation Status
Better Building meets ANSI/ASHRAE Standard 140-2020 requirements for Space-Cooling Equipment Performance Comparative Tests (Section 5.3). Testing demonstrates:
✓ All 25 comparative test cases completed successfully
✓ Physical reasonableness across all operating conditions
✓ Appropriate response to outdoor air, infiltration, and economizer control
✓ Consistent equipment cycling and part-load operation
✓ Proper indoor temperature and humidity response
7.2 Validated Capabilities
Better Building accurately simulates:
Direct expansion (DX) cooling coil performance under dynamic conditions
Empirically-derived equipment performance maps with varying operating conditions
Outdoor air mixing and damper control
Economizer control (ODB/IDB and enthalpy-based strategies)
Sensible and latent cooling loads with hourly variation
Part-load equipment operation and cycling losses
Variable infiltration rates and mechanical ventilation
Thermostat control strategies with varying setpoints
Indoor air temperature and humidity response
Coefficient of performance under variable conditions
7.3 Appropriate Applications
Based on this validation, Better Building is appropriate for:
Cooling load calculations with outdoor air and economizer control
HVAC equipment performance evaluation under realistic operating conditions
Energy simulation for building design optimization with economizer operation
Cooling energy consumption estimates with infiltration effects
Equipment part-load analysis with dynamic loads
Moisture control and dehumidification assessment
Economizer effectiveness analysis and control strategy evaluation
7.4 Limitations
Equipment Component Breakout: This validation does not provide separate compressor and condenser fan electricity tracking.
Space Heating: This validation focuses exclusively on cooling equipment per Section 5.3 of the standard.
Advanced Controls: Some advanced control strategies may require additional validation.
Transient Analysis: Results represent hourly steady-state conditions; sub-hourly transient effects not evaluated.
7.5 Quality Assurance
This validation is part of Better Building's ongoing quality assurance program including periodic re-validation, regression testing, public documentation, and continuous improvement processes.
8. Modeller Report
Per ASHRAE Standard 140-2020, Section 5.3
8.1 Results Outside Acceptable Ranges
All Better Building results show physical reasonableness and general agreement with comparative program results. No results were omitted as unreasonable or unrealistic.
8.2 Omitted Test Cases
Test cases not omitted. All 25 comparative test cases from ASHRAE Standard 140-2020, Section 5.3 completed.
Note on Compressor/Condenser Fan Breakout: Separate compressor and condenser fan electricity results not available due to EnergyPlus DX coil model structure; this is consistent with limitations noted in the standard.
8.3 Alternative Modelling Methods
No alternative modelling methods were required. All test specifications in ASHRAE Standard 140-2020, Section 5.3 were modelled as specified using native Better Building/EnergyPlus functionality.
8.4 Non-Specified Inputs
No non-specified inputs were required. All inputs were taken directly from ASHRAE Standard 140-2020 specifications.
8.5 Software Modifications
No modifications to Better Building source code were required. All testing was performed using the standard publicly-available release version with EnergyPlus v25.1.
8.6 Anomalous Results
No anomalous results were observed. All Better Building results show expected physical behaviours and reasonable agreement with comparative program results across all test cases.
8.7 Summary
Compliance Status
Better Building meets ANSI/ASHRAE Standard 140-2020 Section 5.3 requirements
Exceptions
None
Recommended Actions
None
9. Software Information
9.1 Software Identification
Vendor
Better Building
Address
Melbourne, Australia
Website
www.betterbuilding.io
Contact
Darren O'Dea
Software Name
Better Building
Simulation Engine
EnergyPlus v25.1
Testing Date
15/11/25 - 17/11/25
Report Date
17/11/25
9.2 System Requirements
Operating System
Windows 10/11 (64-bit)
RAM
4 GB minimum (8 GB recommended)
Hard Disk
N/A
Display
1920×1080 resolution recommended
Graphics
OpenGL compatible graphics card
Required Software
EnergyPlus (included with installation)
9.3 Software Availability
Commercial Availability
Online
Documentation
https://docs.betterbuilding.io/
Technical Support
Ticket Support
Training
On-demand Courses
10. References
10.1 Standards
ANSI/ASHRAE. 2020. ANSI/ASHRAE Standard 140-2020: Standard Method of Test for the Evaluation of Building Energy Analysis Computer Programs. Section 5.3: Space-Cooling Equipment Performance Tests. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, GA.
10.2 Software Documentation
U.S. Department of Energy. EnergyPlus Version v25.1 Documentation. Available at: https://energyplus.net/documentation
10.3 Related Publications
ASHRAE. 2021. 2021 ASHRAE Handbook—Fundamentals. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, GA.
ISO. 2017. ISO 13790:2008 Energy performance of buildings -- Calculation of energy use for space heating and cooling. International Organisation for Standardisation, Geneva, Switzerland.
11. Document Control
Revision History
1.0
17.11.25
DOD
Initial release
1.1
25.11.25
DOD
Corrected section references from Section 9 to Section 5.3 per ASHRAE Standard 140-2020 structure verification
Last updated
Was this helpful?

