# J4D6 Walls and glazing

## What is J4D6 Walls and Glazing?

J4D6 Walls and Glazing outlines the energy efficiency requirements for wall-glazing construction, focusing on both thermal and solar performance. Key points include:

### Total System U-Value:

* Wall-glazing constructions must meet specific U-Value limits, which represent the overall thermal conductivity of the system. The limits vary by building classification:
  * For Class 2 common areas and Classes 5, 6, 7, 8, 9b, and non-ward areas of Class 9a buildings: U2.0.
  * For Class 3, 9c, and ward areas of Class 9a buildings:
    * U1.1 in climate zones 1, 3, 4, 6, or 7.
    * U2.0 in climate zones 2 or 5.
    * U0.9 in climate zone 8.
* Display glazing is limited to U5.8.

### Calculation of U-Value:&#x20;

The U-Value for wall-glazing construction must be calculated according to Specification 37.

### Wall Components' R-Value:&#x20;

Wall components must achieve a minimum Total R-Value based on the percentage of wall area in the wall-glazing construction:

* If less than 80% of the area: R1.0.
* If 80% or more of the area: the value specified in Table J4D6a.

#### Table J4D6a Minimum wall Total R-Value - Wall area 80% or more of wall-glazing construction area

<table><thead><tr><th width="173">Climate zone</th><th width="294">Class 2 common area, Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area</th><th>Class 3 or 9c building or Class 9a ward area</th></tr></thead><tbody><tr><td>1</td><td>2.4</td><td>3.3</td></tr><tr><td>2</td><td>1.4</td><td>1.4</td></tr><tr><td>3</td><td>1.4</td><td>3.3</td></tr><tr><td>4</td><td>1.4</td><td>2.8</td></tr><tr><td>5</td><td>1.4</td><td>1.4</td></tr><tr><td>6</td><td>1.4</td><td>2.8</td></tr><tr><td>7</td><td>1.4</td><td>2.8</td></tr><tr><td>8</td><td>1.4</td><td>3.8</td></tr></tbody></table>

### Solar Admittance:

* Externally facing wall-glazing constructions (excluding wholly internal ones) must meet solar admittance limits specified in Table J4D6b for Class 2 common areas and Classes 5, 6, 7, 8, 9b, and non-ward areas of Class 9a buildings, and Table J4D6c for Class 3, 9c, and ward areas of Class 9a buildings.
* Solar admittance must be calculated according to Specification 37.

#### Table J4D6b Maximum wall-glazing construction solar admittance - Class 2 common area, Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area

| Climate zone | Eastern aspect solar admittance | Northern aspect solar admittance | Southern aspect solar admittance | Western aspect solar admittance |
| ------------ | ------------------------------- | -------------------------------- | -------------------------------- | ------------------------------- |
| 1            | 0.12                            | 0.12                             | 0.12                             | 0.12                            |
| 2            | 0.13                            | 0.13                             | 0.13                             | 0.13                            |
| 3            | 0.16                            | 0.16                             | 0.16                             | 0.16                            |
| 4            | 0.13                            | 0.13                             | 0.13                             | 0.13                            |
| 5            | 0.13                            | 0.13                             | 0.13                             | 0.13                            |
| 6            | 0.13                            | 0.13                             | 0.13                             | 0.13                            |
| 7            | 0.13                            | 0.13                             | 0.13                             | 0.13                            |
| 8            | 0.20                            | 0.20                             | 0.42                             | 0.36                            |

#### Table J4D6c Maximum wall-glazing construction solar admittance - Class 3 or 9c building or Class 9a ward area

| Climate zone | Eastern aspect solar admittance | Northern aspect solar admittance | Southern aspect solar admittance | Western aspect solar admittance |
| ------------ | ------------------------------- | -------------------------------- | -------------------------------- | ------------------------------- |
| 1            | 0.07                            | 0.07                             | 0.10                             | 0.07                            |
| 2            | 0.10                            | 0.10                             | 0.10                             | 0.10                            |
| 3            | 0.07                            | 0.07                             | 0.07                             | 0.07                            |
| 4            | 0.07                            | 0.07                             | 0.07                             | 0.07                            |
| 5            | 0.10                            | 0.10                             | 0.10                             | 0.10                            |
| 6            | 0.07                            | 0.07                             | 0.07                             | 0.07                            |
| 7            | 0.07                            | 0.07                             | 0.07                             | 0.07                            |
| 8            | 0.08                            | 0.08                             | 0.08                             | 0.08                            |

5. SHGC for Display Glazing: The Total System SHGC (Solar Heat Gain Coefficient) of display glazing must not exceed 0.81 divided by the applicable shading factor outlined in S37C7.

#### Table S37C7a Shading multipliers — Northern, eastern and western aspects

| G/H | P/H = 0 | P/H = 0.1 | P/H = 0.2 | P/H = 0.3 | P/H = 0.4 | P/H = 0.5 | P/H = 0.6 | P/H = 0.7 | P/H = 0.8 | P/H = 0.9 | P/H = 1 |
| --- | ------- | --------- | --------- | --------- | --------- | --------- | --------- | --------- | --------- | --------- | ------- |
| 0   | 1.00    | 0.90      | 0.80      | 0.72      | 0.64      | 0.57      | 0.51      | 0.46      | 0.41      | 0.38      | 0.35    |
| 0.1 | 1.00    | 0.95      | 0.89      | 0.81      | 0.74      | 0.66      | 0.59      | 0.52      | 0.47      | 0.42      | 0.40    |
| 0.2 | 1.00    | 0.98      | 0.94      | 0.89      | 0.82      | 0.75      | 0.68      | 0.62      | 0.56      | 0.51      | 0.47    |
| 0.3 | 1.00    | 1.00      | 0.97      | 0.94      | 0.89      | 0.84      | 0.78      | 0.72      | 0.66      | 0.61      | 0.57    |
| 0.4 | 1.00    | 1.00      | 1.00      | 0.99      | 0.97      | 0.90      | 0.84      | 0.77      | 0.73      | 0.68      |         |
| 0.5 | 1.00    | 1.00      | 1.00      | 1.00      | 0.99      | 0.97      | 0.92      | 0.90      | 0.86      | 0.83      | 0.79    |

#### Table S37C7b Shading multipliers — Southern aspect

| G/H | P/H = 0 | P/H = 0.1 | P/H = 0.2 | P/H = 0.3 | P/H = 0.4 | P/H = 0.5 | P/H = 0.6 | P/H = 0.7 | P/H = 0.8 | P/H = 0.9 | P/H = 1 |
| --- | ------- | --------- | --------- | --------- | --------- | --------- | --------- | --------- | --------- | --------- | ------- |
| 0   | 1.00    | 0.93      | 0.87      | 0.82      | 0.77      | 0.73      | 0.69      | 0.65      | 0.62      | 0.60      | 0.58    |
| 0.1 | 1.00    | 0.97      | 0.93      | 0.88      | 0.84      | 0.79      | 0.75      | 0.71      | 0.67      | 0.64      | 0.62    |
| 0.2 | 1.00    | 0.98      | 0.96      | 0.93      | 0.89      | 0.85      | 0.81      | 0.77      | 0.73      | 0.70      | 0.68    |
| 0.3 | 1.00    | 0.99      | 0.98      | 0.96      | 0.93      | 0.90      | 0.87      | 0.83      | 0.80      | 0.77      | 0.74    |
| 0.4 | 1.00    | 1.00      | 0.99      | 0.98      | 0.96      | 0.94      | 0.91      | 0.89      | 0.86      | 0.84      | 0.81    |
| 0.5 | 1.00    | 1.00      | 0.99      | 0.99      | 0.98      | 0.96      | 0.95      | 0.93      | 0.91      | 0.90      | 0.88    |

### J4D6 Walls and glazing on Better Building

Speckel automatically checks the provisions of J4D6 Walls and glazing against your design, as per Specification 37 Calculation of U-Value and solar admittance. Models can be simulated with simple DTS shading multipliers (Table S37C7a  + S37C7b) or can be generated to produce a Performance Solution.