Prescriptive Building Envelope Compliance Path

Building Envelope Requirements

These tables specify the maximum assembly U-factors, minimum insulation R-values, and other thermal requirements for building envelope components by climate zone and space conditioning category. These tables specify the maximum thermal performance requirements used to establish the baseline envelope in trade-off compliance calculations. The baseline design uses these maximum allowable values to create a reference against which the proposed design is compared.

Climate Zone 0 (A,B)

Opaque Elements - Nonresidential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.220

R-4.4 c.i.

Metal building*

U-0.233

R-1.8 + R-3.3 FC

Attic and other

U-0.153

R-6.7

Walls, Above Grade

Mass

U-3.293

NR

Metal building

U-0.533

R-0 + R-1.7 c.i.

Steel-framed

U-0.705

R-2.3

Wood-framed and other

U-0.504

R-2.3

Wall, Below Grade

Below-grade wall

C-6.473

NR

Floors

Mass

U-1.825

NR

Steel joist

U-1.986

NR

Wood-framed and other

U-1.599

NR

Slab-on-Grade Floors

Unheated

F-1.264

NR

Heated

F-1.766

R-1.3 for 300 mm

Opaque Doors

Swinging

U-2.101

Non-swinging

U-1.760

c.i. = continuous insulation (see Section 3.2)

FC = filled cavity (see Section A2.3.2.5)

Ls = liner system (see Section A2.3.2.4)

NR = no (insulation) requirement

* When using the R-value compliance method for metal building roofs, a thermal spacer block is required (see Section A2.3.2).

** Exception to Section 5.5.3.2 applies for mass walls above grade (Climate Zones 0, 1, 2, 5, and 6 only).

Opaque Elements - Residential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.184

R-5.3 c.i.

Metal building*

U-0.233

R-1.8 + R-3.3 FC

Attic and other

U-0.153

R-6.7

Walls, Above Grade

Mass**

U-0.857

R-1.0 c.i.

Metal building

U-0.533

R-0 + R-1.7 c.i.

Steel-framed

U-0.705

R-2.3

Wood-framed and other

U-0.504

R-2.3

Wall, Below Grade

Below-grade wall

C-6.473

NR

Floors

Mass

U-1.825

NR

Steel joist

U-1.986

NR

Wood-framed and other

U-1.599

NR

Slab-on-Grade Floors

Unheated

F-1.264

NR

Heated

F-1.766

R-1.3 for 300 mm

Opaque Doors

Swinging

U-2.101

Non-swinging

U-1.760

Opaque Elements - Semi-heated

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-1.240

R-0.7 c.i.

Metal building

U-0.653

R-1.8

Attic and other

U-0.459

R-2.3

Walls, Above Grade

Mass

U-3.293

NR

Metal building

U-1.998

NR

Steel-framed

U-1.998

NR

Wood-framed and other

U-1.660

NR

Wall, Below Grade

Below-grade wall

C-6.473

NR

Floors

Mass

U-1.825

NR

Steel joist

U-1.986

NR

Wood-framed and other

U-1.599

NR

Slab-on-Grade Floors

Unheated

F-1.264

NR

Heated

F-1.766

R-1.3 for 300 mm

Opaque Doors

Swinging

U-3.975

Non-swinging

U-8.233

Fenestration - Climate Zone 0

Vertical Fenestration (0% to 40% of Wall)

Space Type
Fenestration Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

Fixed

2.84

0.22

1.10

Operable

3.52

0.20

1.10

Entrance door

4.71

0.20

1.10

Residential

Fixed

2.84

0.22

1.10

Operable

3.52

0.20

1.10

Entrance door

4.71

0.20

1.10

Semiheated

Fixed

2.84

NR

NR

Operable

3.69

NR

NR

Entrance door

6.25

NR

NR

Skylights (0% to 3% of Roof)

Space Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

3.97

0.30

NR

Residential

3.97

0.30

NR

Semi-heated

10.22

NR

NR


Climate Zone 1 (A,B)

Opaque Elements - Nonresidential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.273

R-3.5 c.i.

Metal building*

U-0.233

R-1.8 + R-3.3 FC

Attic and other

U-0.153

R-6.7

Walls, Above Grade

Mass

U-3.293

NR

Metal building

U-0.533

R-0 + R-1.7 c.i.

Steel-framed

U-0.705

R-2.3

Wood-framed and other

U-0.504

R-2.3

Wall, Below Grade

Below-grade wall

C-6.473

NR

Floors

Mass

U-1.825

NR

Steel joist

U-1.986

NR

Wood-framed and other

U-1.599

NR

Slab-on-Grade Floors

Unheated

F-1.264

NR

Heated

F-1.766

R-1.3 for 300 mm

Opaque Doors

Swinging

U-2.101

Non-swinging

U-1.760

Opaque Elements - Residential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.220

R-4.4 c.i.

Metal building*

U-0.233

R-1.8 + R-3.3 FC

Attic and other

U-0.153

R-6.7

Walls, Above Grade

Mass**

U-0.857

R-1.0 c.i.

Metal building

U-0.533

R-0 + R-1.7 c.i.

Steel-framed

U-0.705

R-2.3

Wood-framed and other

U-0.504

R-2.3

Wall, Below Grade

Below-grade wall

C-6.473

NR

Floors

Mass

U-1.825

NR

Steel joist

U-1.986

NR

Wood-framed and other

U-1.599

NR

Slab-on-Grade Floors

Unheated

F-1.264

NR

Heated

F-1.766

R-1.3 for 300 mm

Opaque Doors

Swinging

U-2.101

Non-swinging

U-1.760

Opaque Elements - Semiheated

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-1.240

R-0.7 c.i.

Metal building

U-0.653

R-1.8

Attic and other

U-0.459

R-2.3

Walls, Above Grade

Mass

U-3.293

NR

Metal building

U-1.998

NR

Steel-framed

U-1.998

NR

Wood-framed and other

U-1.660

NR

Wall, Below Grade

Below-grade wall

C-6.473

NR

Floors

Mass

U-1.825

NR

Steel joist

U-1.986

NR

Wood-framed and other

U-1.599

NR

Slab-on-Grade Floors

Unheated

F-1.264

NR

Heated

F-1.766

R-1.3 for 300 mm

Opaque Doors

Swinging

U-3.975

Non-swinging

U-8.233

Fenestration - Climate Zone 1

Vertical Fenestration (0% to 40% of Wall)

Space Type
Fenestration Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

Fixed

2.84

0.23

1.10

Operable

3.52

0.21

1.10

Entrance door

4.71

0.21

1.10

Residential

Fixed

2.84

0.23

1.10

Operable

3.52

0.21

1.10

Entrance door

4.71

0.21

1.10

Semiheated

Fixed

6.81

NR

NR

Operable

6.81

NR

NR

Entrance door

6.25

NR

NR

Skylights (0% to 3% of Roof)

Space Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

3.97

0.30

NR

Residential

3.97

0.30

NR

Semi-heated

10.22

NR

NR


Climate Zone 2 (A,B)

Opaque Elements - Nonresidential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.220

R-4.4 c.i.

Metal building*

U-0.233

R-1.8 + R-3.3 FC

Attic and other

U-0.153

R-6.7

Walls, Above Grade

Mass**

U-0.857

R-1.0 c.i.

Metal building

U-0.533

R-0 + R-1.7 c.i.

Steel-framed

U-0.479

R-2.3 + R-0.7 c.i.

Wood-framed and other

U-0.504

R-2.3

Wall, Below Grade

Below-grade wall

C-6.473

NR

Floors

Mass

U-0.606

R-1.9

Steel joist

U-0.214

R-5.3

Wood-framed and other

U-0.188

R-5.3

Slab-on-Grade Floors

Unheated

F-1.264

NR

Heated

F-1.558

R-1.8 for 600 mm

Opaque Doors

Swinging

U-2.101

Non-swinging

U-1.760

Opaque Elements - Residential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.220

R-4.4 c.i.

Metal building*

U-0.233

R-1.8 + R-3.3 FC

Attic and other

U-0.153

R-6.7

Walls, Above Grade

Mass

U-0.701

R-1.3 c.i.

Metal building

U-0.533

R-0 + R-1.7 c.i.

Steel-framed

U-0.365

R-2.3 + R-1.3 c.i.

Wood-framed and other

U-0.504

R-2.3

Wall, Below Grade

Below-grade wall

C-6.473

NR

Floors

Mass

U-0.496

R-1.5

Steel joist

U-0.214

R-5.3

Wood-framed and other

U-0.188

R-5.3

Slab-on-Grade Floors

Unheated

F-1.264

NR

Heated

F-1.489

R-2.6 for 600 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-1.760

Opaque Elements - Semi-heated

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.982

R-0.9 c.i.

Metal building

U-0.545

R-2.8

Attic and other

U-0.300

R-3.3

Walls, Above Grade

Mass

U-3.293

NR

Metal building

U-0.920

R-2.3

Steel-framed

U-0.705

R-2.3

Wood-framed and other

U-0.504

R-2.3

Wall, Below Grade

Below-grade wall

C-6.473

NR

Floors

Mass

U-1.825

NR

Steel joist

U-0.390

R-2.3

Wood-framed and other

U-0.376

R-2.3

Slab-on-Grade Floors

Unheated

F-1.264

NR

Heated

F-1.766

R-1.3 for 300 mm

Opaque Doors

Swinging

U-3.975

Non-swinging

U-8.233

Fenestration - Climate Zone 2

Vertical Fenestration (0% to 40% of Wall)

Space Type
Fenestration Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

Fixed

2.56

0.25

1.10

Operable

3.41

0.23

1.10

Entrance door

4.37

0.23

1.10

Residential

Fixed

2.56

0.25

1.10

Operable

3.41

0.23

1.10

Entrance door

4.37

0.23

1.10

Semiheated

Fixed

2.84

NR

NR

Operable

3.69

NR

NR

Entrance door

4.37

NR

NR

Skylights (0% to 3% of Roof)

Space Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

3.69

0.30

NR

Residential

3.69

0.30

NR

Semi-heated

5.11

NR

NR


Climate Zone 3 (A,B,C)

Opaque Elements - Nonresidential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.220

R-4.4 c.i.

Metal building*

U-0.233

R-1.8 + R-3.3 FC

Attic and other

U-0.153

R-6.7

Walls, Above Grade

Mass

U-0.701

R-1.3 c.i.

Metal building

U-0.533

R-0 + R-1.7 c.i.

Steel-framed

U-0.435

R-2.3 + R-0.9 c.i.

Wood-framed and other

U-0.504

R-2.3

Wall, Below Grade

Below-grade wall

C-6.473

NR

Floors

Mass

U-0.420

R-1.8 c.i.

Steel joist

U-0.214

R-5.3

Wood-framed and other

U-0.188

R-5.3

Slab-on-Grade Floors

Unheated

F-1.264

NR

Heated

F-1.489

R-2.6 for 600 mm

Opaque Doors

Swinging

U-2.101

Non-swinging

U-1.760

Opaque Elements - Residential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.220

R-4.4 c.i.

Metal building*

U-0.233

R-1.8 + R-3.3 FC

Attic and other

U-0.153

R-6.7

Walls, Above Grade

Mass

U-0.592

R-1.7 c.i.

Metal building

U-0.410

R-0 + R-2.3 c.i.

Steel-framed

U-0.365

R-2.3 + R-1.3 c.i.

Wood-framed and other

U-0.365

R-2.3 + R-0.7 c.i. or R-3.5

Wall, Below Grade

Below-grade wall

C-6.473

NR

Floors

Mass

U-0.420

R-1.8 c.i.

Steel joist

U-0.214

R-5.3

Wood-framed and other

U-0.188

R-5.3

Slab-on-Grade Floors

Unheated

F-0.935

R-1.8 for 600 mm

Heated

F-1.489

R-2.6 for 600 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-1.760

Opaque Elements - Semiheated

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.677

R-1.3 c.i.

Metal building

U-0.545

R-2.8

Attic and other

U-0.300

R-3.3

Walls, Above Grade

Mass

U-3.293

NR

Metal building

U-0.920

R-2.3

Steel-framed

U-0.705

R-2.3

Wood-framed and other

U-0.504

R-2.3

Wall, Below Grade

Below-grade wall

C-6.473

NR

Floors

Mass

U-0.780

R-0.7 c.i.

Steel joist

U-0.296

R-3.3

Wood-framed and other

U-0.288

R-3.3

Slab-on-Grade Floors

Unheated

F-1.264

NR

Heated

F-1.766

R-1.3 for 300 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-2.044

Fenestration - Climate Zone 3

Vertical Fenestration (0% to 40% of Wall)

Space Type
Fenestration Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

Fixed

2.38

0.25

1.10

Operable

3.07

0.23

1.10

Entrance door

3.86

0.23

1.10

Residential

Fixed

2.38

0.25

1.10

Operable

3.07

0.23

1.10

Entrance door

3.86

0.23

1.10

Semiheated

Fixed

2.84

NR

NR

Operable

3.69

NR

NR

Entrance door

4.37

NR

NR

Skylights (0% to 3% of Roof)

Space Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

3.12

0.30

NR

Residential

3.12

0.30

NR

Semiheated

5.11

NR

NR


Climate Zone 4 (A,B,C)

Opaque Elements - Nonresidential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.184

R-5.3 c.i.

Metal building*

U-0.210

R-3.3 + R-1.9 Ls or R-4.4 + R-1.4 Ls

Attic and other

U-0.119

R-8.6

Walls, Above Grade

Mass

U-0.592

R-1.7 c.i.

Metal building

U-0.341

R-0 + R-2.8 c.i.

Steel-framed

U-0.365

R-2.3 + R-1.3 c.i.

Wood-framed and other

U-0.365

R-2.3 + R-0.7 c.i. or R-3.5

Wall, Below Grade

Below-grade wall

C-0.678

R-1.3 c.i.

Floors

Mass

U-0.321

R-2.6 c.i.

Steel joist

U-0.214

R-5.3

Wood-framed and other

U-0.188

R-5.3

Slab-on-Grade Floors

Unheated

F-0.900

R-2.6 for 600 mm

Heated

F-1.459

R-3.5 for 600 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-1.760

Opaque Elements - Residential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.184

R-5.3 c.i.

Metal building*

U-0.210

R-3.3 + R-1.9 Ls or R-4.4 + R-1.4 Ls

Attic and other

U-0.119

R-8.6

Walls, Above Grade

Mass

U-0.513

R-2.0 c.i.

Metal building

U-0.286

R-0 + R-3.3 c.i.

Steel-framed

U-0.365

R-2.3 + R-1.3 c.i.

Wood-framed and other

U-0.365

R-2.3 + R-0.7 c.i. or R-3.5

Wall, Below Grade

Below-grade wall

C-0.522

R-1.8 c.i.

Floors

Mass

U-0.287

R-2.9 c.i.

Steel joist

U-0.214

R-5.3

Wood-framed and other

U-0.188

R-5.3

Slab-on-Grade Floors

Unheated

F-0.900

R-2.6 for 600 mm

Heated

F-1.191

R-3.5 for 1200 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-1.760

Opaque Elements - Semiheated

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.527

R-1.8 c.i.

Metal building

U-0.466

R-3.3

Attic and other

U-0.192

R-5.3

Walls, Above Grade

Mass

U-3.293

NR

Metal building

U-0.920

R-2.3

Steel-framed

U-0.705

R-2.3

Wood-framed and other

U-0.504

R-2.3

Wall, Below Grade

Below-grade wall

C-6.473

NR

Floors

Mass

U-0.606

R-1.1 c.i.

Steel joist

U-0.296

R-3.3

Wood-framed and other

U-0.288

R-3.3

Slab-on-Grade Floors

Unheated

F-1.264

NR

Heated

F-1.558

R-1.8 for 600 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-2.044

Fenestration - Climate Zone 4

Vertical Fenestration (0% to 40% of Wall)

Space Type
Fenestration Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

Fixed

2.04

0.36

1.10

Operable

2.56

0.33

1.10

Entrance door

3.58

0.33

1.10

Residential

Fixed

2.04

0.36

1.10

Operable

2.56

0.33

1.10

Entrance door

3.58

0.33

1.10

Semiheated

Fixed

2.84

NR

NR

Operable

3.69

NR

NR

Entrance door

4.37

NR

NR

Skylights (0% to 3% of Roof)

Space Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

2.84

0.40

NR

Residential

2.84

0.40

NR

Semiheated

4.26

NR

NR


Climate Zone 5 (A,B,C)

Opaque Elements - Nonresidential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.184

R-5.3 c.i.

Metal building*

U-0.210

R-3.3 + R-1.9 Ls or R-4.4 + R-1.4 Ls

Attic and other

U-0.119

R-8.6

Walls, Above Grade

Mass

U-0.513

R-2.0 c.i.

Metal building

U-0.286

R-0 + R-3.3 c.i.

Steel-framed

U-0.315

R-2.3 + R-1.8 c.i.

Wood-framed and other

U-0.291

R-2.3 + R-0.9 c.i. or R-3.3 + R-0.9 c.i.

Wall, Below Grade

Below-grade wall

C-0.678

R-1.3 c.i.

Floors

Mass

U-0.321

R-2.6 c.i.

Steel joist

U-0.214

R-5.3

Wood-framed and other

U-0.188

R-6.7

Slab-on-Grade Floors

Unheated

F-0.900

R-2.6 for 600 mm

Heated

F-1.191

R-3.5 for 1200 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-1.760

Opaque Elements - Residential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.184

R-5.3 c.i.

Metal building*

U-0.210

R-3.3 + R-1.9 Ls or R-4.4 + R-1.4 Ls

Attic and other

U-0.119

R-8.6

Walls, Above Grade

Mass

U-0.453

R-2.3 c.i.

Metal building

U-0.286

R-0 + R-3.3 c.i.

Steel-framed

U-0.315

R-2.3 + R-1.8 c.i.

Wood-framed and other

U-0.291

R-2.3 + R-0.9 c.i. or R-3.3 + R-0.9 c.i.

Wall, Below Grade

Below-grade wall

C-0.522

R-1.8 c.i.

Floors

Mass

U-0.287

R-2.9 c.i.

Steel joist

U-0.214

R-5.3

Wood-framed and other

U-0.188

R-6.7

Slab-on-Grade Floors

Unheated

F-0.882

R-3.5 for 600 mm

Heated

F-1.191

R-3.5 for 1200 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-1.760

Opaque Elements - Semiheated

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.360

R-2.6 c.i.

Metal building

U-0.466

R-3.3

Attic and other

U-0.192

R-5.3

Walls, Above Grade

Mass**

U-0.857

R-1.0 c.i.

Metal building

U-0.533

R-0 + R-1.7 c.i.

Steel-framed

U-0.479

R-2.3 + R-0.7 c.i.

Wood-framed and other

U-0.504

R-2.3

Wall, Below Grade

Below-grade wall

C-6.473

NR

Floors

Mass

U-0.606

R-1.1 c.i.

Steel joist

U-0.296

R-3.3

Wood-framed and other

U-0.288

R-3.3

Slab-on-Grade Floors

Unheated

F-1.264

NR

Heated

F-1.558

R-1.8 for 600 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-2.044

Fenestration - Climate Zone 5

Vertical Fenestration (0% to 40% of Wall)

Space Type
Fenestration Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

Fixed

2.04

0.38

1.10

Operable

2.56

0.33

1.10

Entrance door

3.58

0.33

1.10

Residential

Fixed

2.04

0.38

1.10

Operable

2.56

0.33

1.10

Entrance door

3.58

0.33

1.10

Semiheated

Fixed

2.84

NR

NR

Operable

3.69

NR

NR

Entrance door

4.37

NR

NR

Skylights (0% to 3% of Roof)

Space Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

2.84

0.40

NR

Residential

2.84

0.40

NR

Semiheated

4.26

NR

NR


Climate Zone 6 (A,B)

Opaque Elements - Nonresidential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.184

R-5.3 c.i.

Metal building*

U-0.175

R-4.4 + R-1.9 Ls

Attic and other

U-0.119

R-8.6

Walls, Above Grade

Mass

U-0.453

R-2.3 c.i.

Metal building

U-0.286

R-0 + R-3.3 c.i.

Steel-framed

U-0.277

R-2.3 + R-2.2 c.i.

Wood-framed and other

U-0.291

R-2.3 + R-1.3 c.i. or R-3.3 + R-0.9 c.i.

Wall, Below Grade

Below-grade wall

C-0.522

R-1.8 c.i.

Floors

Mass

U-0.287

R-2.9 c.i.

Steel joist

U-0.183

R-6.7

Wood-framed and other

U-0.153

R-6.7

Slab-on-Grade Floors

Unheated

F-0.882

R-3.5 for 600 mm

Heated

F-1.191

R-3.5 for 1200 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-1.760

Opaque Elements - Residential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.184

R-5.3 c.i.

Metal building*

U-0.163

R-5.3 + R-1.9 Ls

Attic and other

U-0.119

R-8.6

Walls, Above Grade

Mass

U-0.404

R-2.7 c.i.

Metal building

U-0.286

R-0 + R-3.3 c.i.

Steel-framed

U-0.277

R-2.3 + R-2.2 c.i.

Wood-framed and other

U-0.291

R-2.3 + R-1.3 c.i. or R-3.3 + R-0.9 c.i.

Wall, Below Grade

Below-grade wall

C-0.358

R-2.6 c.i.

Floors

Mass

U-0.287

R-2.9 c.i.

Steel joist

U-0.183

R-6.7

Wood-framed and other

U-0.153

R-6.7

Slab-on-Grade Floors

Unheated

F-0.750

R-3.5 for 1200 mm

Heated

F-1.162

R-4.4 for 1200 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-1.760

Opaque Elements - Semiheated

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.360

R-2.6 c.i.

Metal building

U-0.341

R-3.3 + R-3.3

Attic and other

U-0.192

R-5.3

Walls, Above Grade

Mass**

U-0.857

R-1.0 c.i.

Metal building

U-0.533

R-0 + R-1.7 c.i.

Steel-framed

U-0.479

R-2.3 + R-0.7 c.i.

Wood-framed and other

U-0.504

R-2.3

Wall, Below Grade

Below-grade wall

C-0.678

R-1.3 c.i.

Floors

Mass

U-0.496

R-1.5 c.i.

Steel joist

U-0.296

R-3.3

Wood-framed and other

U-0.288

R-3.3

Slab-on-Grade Floors

Unheated

F-1.264

NR

Heated

F-1.489

R-2.6 for 600 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-2.044

Fenestration - Climate Zone 6

Vertical Fenestration (0% to 40% of Wall)

Space Type
Fenestration Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

Fixed

1.93

0.38

1.10

Operable

2.38

0.34

1.10

Entrance door

3.58

0.34

1.10

Residential

Fixed

1.93

0.38

1.10

Operable

2.38

0.34

1.10

Entrance door

3.58

0.34

1.10

Semiheated

Fixed

2.21

NR

NR

Operable

2.73

NR

NR

Entrance door

3.86

NR

NR

Skylights (0% to 3% of Roof)

Space Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

2.67

0.40

NR

Residential

2.84

0.40

NR

Semiheated

4.26

NR

NR


Climate Zone 7

Opaque Elements - Nonresidential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.158

R-6.2 c.i.

Metal building*

U-0.163

R-5.3 + R-1.9 Ls

Attic and other

U-0.098

R-10.6

Walls, Above Grade

Mass

U-0.404

R-2.7 c.i.

Metal building

U-0.248

R-0 + R-3.9 c.i.

Steel-framed

U-0.277

R-2.3 + R-2.2 c.i.

Wood-framed and other

U-0.291

R-2.3 + R-1.3 c.i. or R-3.3 + R-0.9 c.i.

Wall, Below Grade

Below-grade wall

C-0.358

R-2.6 c.i.

Floors

Mass

U-0.236

R-3.7 c.i.

Steel joist

U-0.183

R-6.7

Wood-framed and other

U-0.153

R-6.7

Slab-on-Grade Floors

Unheated

F-0.882

R-3.5 for 600 mm

Heated

F-1.162

R-4.4 for 1200 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-1.760

Opaque Elements - Residential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.158

R-6.2 c.i.

Metal building*

U-0.163

R-5.3 + R-1.9 Ls

Attic and other

U-0.098

R-10.6

Walls, Above Grade

Mass

U-0.404

R-2.7 c.i.

Metal building

U-0.248

R-0 + R-3.9 c.i.

Steel-framed

U-0.240

R-2.3 + R-2.7 c.i.

Wood-framed and other

U-0.291

R-2.3 + R-1.3 c.i. or R-3.3 + R-0.9 c.i.

Wall, Below Grade

Below-grade wall

C-0.358

R-2.6 c.i.

Floors

Mass

U-0.236

R-3.7 c.i.

Steel joist

U-0.183

R-6.7

Wood-framed and other

U-0.153

R-6.7

Slab-on-Grade Floors

Unheated

F-0.750

R-3.5 for 1200 mm

Heated

F-1.162

R-4.4 for 1200 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-1.760

Opaque Elements - Semiheated

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.220

R-4.4 c.i.

Metal building

U-0.210

R-3.3 + R-1.9 Ls or R-4.4 + R-1.4 Ls

Attic and other

U-0.153

R-6.7 c.i.

Walls, Above Grade

Mass

U-0.701

R-1.3 c.i.

Metal building

U-0.410

R-0 + R-2.3 c.i.

Steel-framed

U-0.365

R-2.3 + R-1.3 c.i.

Wood-framed and other

U-0.365

R-2.3 + R-0.7 c.i.

Wall, Below Grade

Below-grade wall

C-0.678

R-1.3 c.i.

Floors

Mass

U-0.420

R-1.8 c.i.

Steel joist

U-0.296

R-3.3

Wood-framed and other

U-0.288

R-3.3

Slab-on-Grade Floors

Unheated

F-1.264

NR

Heated

F-1.489

R-2.6 for 600 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-1.760

Fenestration - Climate Zone 7

Vertical Fenestration (0% to 40% of Wall)

Space Type
Fenestration Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

Fixed

1.65

0.40

1.10

Operable

2.04

0.36

1.10

Entrance door

3.58

0.36

1.10

Residential

Fixed

1.65

0.40

1.10

Operable

2.04

0.36

1.10

Entrance door

3.58

0.36

1.10

Semiheated

Fixed

2.04

NR

NR

Operable

2.50

NR

NR

Entrance door

3.58

NR

NR

Skylights (0% to 3% of Roof)

Space Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

2.50

NR

NR

Residential

2.50

NR

NR

Semiheated

4.26

NR

NR


Climate Zone 8

Opaque Elements - Nonresidential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.158

R-6.2 c.i.

Metal building*

U-0.147

R-4.4 + R-1.9 + R-1.9 Ls

Attic and other

U-0.098

R-10.6

Walls, Above Grade

Mass

U-0.273

R-3.3 c.i.

Metal building

U-0.220

R-0 + R-4.4 c.i.

Steel-framed

U-0.212

R-2.3 + R-3.3 c.i.

Wood-framed and other

U-0.182

R-2.3 + R-3.3 c.i.

Wall, Below Grade

Below-grade wall

C-0.358

R-2.6 c.i.

Floors

Mass

U-0.217

R-4.1 c.i.

Steel joist

U-0.183

R-6.7

Wood-framed and other

U-0.153

R-6.7

Slab-on-Grade Floors

Unheated

F-0.750

R-3.5 for 1200 mm

Heated

F-1.162

R-4.4 for 1200 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-1.760

Opaque Elements - Residential

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.158

R-6.2 c.i.

Metal building*

U-0.147

R-4.4 + R-1.9 + R-1.9 Ls

Attic and other

U-0.098

R-10.6

Walls, Above Grade

Mass

U-0.273

R-3.3 c.i.

Metal building

U-0.220

R-0 + R-4.4 c.i.

Steel-framed

U-0.212

R-2.3 + R-3.3 c.i.

Wood-framed and other

U-0.182

R-2.3 + R-3.3 c.i.

Wall, Below Grade

Below-grade wall

C-0.358

R-2.6 c.i.

Floors

Mass

U-0.217

R-4.1 c.i.

Steel joist

U-0.183

R-6.7

Wood-framed and other

U-0.153

R-6.7

Slab-on-Grade Floors

Unheated

F-0.734

R-4.4 for 1200 mm

Heated

F-0.646

R-3.5 full slab

Opaque Doors

Swinging

U-2.101

Nonswinging

U-1.760

Opaque Elements - Semi-heated

Element
Assembly Maximum
Insulation Min. R-Value

Roofs

Insulation entirely above deck

U-0.220

R-4.4 c.i.

Metal building

U-0.210

R-3.3 + R-1.9 Ls or R-4.4 + R-1.4 Ls

Attic and other

U-0.153

R-6.7 c.i.

Walls, Above Grade

Mass

U-0.592

R-1.7 c.i.

Metal building

U-0.341

R-0 + R-2.8 c.i.

Steel-framed

U-0.365

R-2.3 + R-1.3 c.i.

Wood-framed and other

U-0.291

R-2.3 + R-1.3 c.i.

Wall, Below Grade

Below-grade wall

C-0.678

R-1.3 c.i.

Floors

Mass

U-0.363

R-2.2 c.i.

Steel joist

U-0.296

R-3.3

Wood-framed and other

U-0.188

R-5.3

Slab-on-Grade Floors

Unheated

F-0.935

R-1.8 for 600 mm

Heated

F-1.489

R-2.6 for 600 mm

Opaque Doors

Swinging

U-2.101

Nonswinging

U-1.760

Fenestration - Climate Zone 8

Vertical Fenestration (0% to 40% of Wall)

Space Type
Fenestration Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

Fixed

1.48

0.40

1.10

Operable

1.82

0.36

1.10

Entrance door

3.58

0.36

1.10

Residential

Fixed

1.48

0.40

1.10

Operable

1.82

0.36

1.10

Entrance door

3.58

0.36

1.10

Semiheated

Fixed

2.04

NR

NR

Operable

2.50

NR

NR

Entrance door

3.58

NR

NR

Skylights (0% to 3% of Roof)

Space Type
Assembly Max. U
Assembly Max. SHGC
Assembly Min. VT/SHGC

Nonresidential

2.33

NR

NR

Residential

2.33

NR

NR

Semiheated

4.26

NR

NR

Roof Insulation

All roofs shall comply with the insulation values specified above.

Skylight curbs shall be insulated to the level of roofs with insulation entirely above deck or R-0.9, whichever is less.

Roof Solar Reflectance and Thermal Emittance

Roofs in Climate Zones 0 through 3 shall have one of the following:

Option a: Minimum Aged Reflectance and Emittance

A minimum three-year-aged solar reflectance of 0.55 and a minimum three-year-aged thermal emittance of 0.75 when tested in accordance with CRRC S100.

Option b: Minimum Solar Reflectance Index

A minimum Solar Reflectance Index of 64 when determined in accordance with the Solar Reflectance Index method in ASTM E1980 using a convection coefficient of 12 W/m²·K, based on three-year-aged solar reflectance and three-year-aged thermal emittance tested in accordance with CRRC S100.

Option c: Increased Insulation

Increased roof insulation levels found below.

Climate Zone 0

Nonresidential

Roof Type
Assembly Maximum
Insulation Min. R-Value

Insulation entirely above deck

U-0.153

R-6.4 c.i.

Metal buildings

U-0.159

R-6.2

Residential

Roof Type
Assembly Maximum
Insulation Min. R-Value

Insulation entirely above deck

U-0.153

R-6.4 c.i.

Climate Zones 1 to 3

Nonresidential

Roof Type
Assembly Maximum
Insulation Min. R-Value

Insulation entirely above deck

U-0.170

R-5.8 c.i.

Metal buildings

U-0.159

R-6.2

Residential

Roof Type
Assembly Maximum
Insulation Min. R-Value

Insulation entirely above deck

U-0.165

R-6.0 c.i.

Exceptions

The following roof types are exempt from the solar reflectance and thermal emittance requirements:

Exception
Description

1. Ballasted Roofs

Ballasted roofs with a minimum stone ballast of 83 kg/m² or 112 kg/m² pavers

2. Vegetative Roofs

Vegetative roof systems that contain a minimum thickness of 64 mm of growing medium and covering a minimum of 75% of the roof area with durable plantings

3. Shaded/Covered Roofs

Roofs where a minimum of 75% of the roof area:<br>a. Is shaded during the peak sun angle on June 21 by permanent components or features of the building<br>b. Is covered by offset photovoltaic arrays, building-integrated photovoltaic arrays, or solar air or water collectors<br>c. Is permitted to be interpolated using a combination of (a) and (b) above

4. Steep-Sloped Roofs

Steep-sloped roofs

5. Metal Building Roofs

Low-sloped metal building roofs in Climate Zones 2 and 3

6. Uncooled Spaces

Roofs over ventilated attics, roofs over semi-heated spaces, or roofs over conditioned spaces that are not cooled spaces

7. Asphaltic Membranes

Asphaltic membranes in Climate Zones 2 and 3

circle-check

Fenestration

General

Compliance with U-factors, SHGC, and VT/SHGC shall be demonstrated for the overall fenestration product.

Gross wall areas and gross roof areas shall be calculated separately for each space conditioning category for the purposes of determining compliance.

Exception 1: Area-Weighted Average Within Single Class

If there are multiple assemblies within a single class of construction for a single space conditioning category, it shall be permitted to demonstrate compliance based on an area-weighted average U-factor, SHGC, VT/SHGC, or LSG.

The area-weighted average across multiple classes of construction or multiple space conditioning categories shall not be permitted for use to demonstrate compliance.

Exception 2: Area-Weighted Average for Vertical Fenestration Across Classes

Vertical fenestration shall be permitted to demonstrate compliance based on an area-weighted average U-factor, SHGC, VT/SHGC, or LSG across multiple classes of construction for a single space conditioning category, but not across multiple space conditioning categories.

Fenestration Area

Vertical Fenestration Area

The total vertical fenestration area shall not be greater than that specified in the tables above.

Exception 3: Street-Level Fenestration

Vertical fenestration that is located on the street side of the street-level story only, provided that all of the following criteria are met:

Criterion
Requirement

Height Limit

The street side of the street-level story does not exceed 6 m in height

Shading

The fenestration has a continuous overhang with a weighted average PF greater than 0.5

Area Limit

The fenestration area for the street side of the street-level story is less than 75% of the gross wall area for the street side of the street-level story

Calculation Requirements:

When this exception is used, separate calculations shall be performed for these sections of the building envelope, and these values shall not be averaged with any others for compliance purposes.

No credit shall be given here or elsewhere in the building for not fully utilizing the fenestration area allowed.

Modeling Intent

This exception accommodates the unique needs of street-level retail and commercial spaces that require extensive glazing for visibility and access while maintaining energy performance through height limits, mandatory shading, and area restrictions. The separate calculation requirement prevents this exception from being used to circumvent fenestration limits for other portions of the building.

Maximum Skylight Fenestration Area

The total skylight area shall not be greater than that specified in the tables above.

Exception

The total skylight area is permitted to be increased to no greater than 6% of the gross roof area, provided the skylights meet all of the criteria in Exception 1 below and the total daylight area under skylights is a minimum of half the floor area of the space.

Exception 1: High-Diffusing Skylights with Photocontrols

Skylights are exempt from SHGC requirements provided the following criteria are met:

Criterion
Requirement

a. Haze Value

Glazing material or diffuser with a measured haze value greater than 90% when tested according to ASTM D1003

b. Visible Transmittance

Skylight VT greater than 0.40

c. Lighting Controls

All general lighting in the daylight area under skylights controlled by multilevel photocontrols in accordance with Section 9.4.1.1(f)

Exception 2: Dynamic Glazing

For dynamic glazing, the minimum SHGC shall be used to demonstrate compliance with this section.

Dynamic glazing shall be considered separately from other skylights, and area-weighted averaging with other skylights that are not dynamic glazing shall not be permitted.

circle-check

Last updated

Was this helpful?