ISO 10211 Thermal Bridge Validation Report

Software Version: Better Building Thermx Solver 1.0 I Date of Testing: 28/10/26 I Report Version: 1.0 I Prepared by Darren O'Dea

1. Purpose and Scope

1.1 Introduction

This report records how the two-dimensional solver behind the Better Building detail tool performs against the validation cases of ISO 10211:2007 Annex A. It is written for third-party assurance: each case states how it was modelled, the result at every reference point against the standard's value, and the same model solved in LBNL THERM 7.8 as an independent check.

The detail tool solves with Better Building Thermx Solver 1.0, an independent finite-element solver and checked against THERM 7.8 itself. Window frames are reported separately in the ISO 10077-2 Window Frame Validation Report (version 1.0), and the ISO 14683 junctions in the ISO 10211 / ISO 14683 / ISO 10077-2 thermal-bridge validation report (version 2.0).

Two references are used:

  1. The standard's values: ISO 10211:2007 Annex A: the analytical temperatures of Case 1 and the tabulated temperatures and heat flow of Case 2.

  2. THERM 7.8 itself: the case models are exported from the detail tool as THERM files and solved in the installed THERM 7.8.80.0, so the report also shows whether Better Building Thermx Solver 1.0 gives THERM's own answer on the same model.

1.2 The standard

  • Classification (A.1.1). A two-dimensional calculation method is a steady-state high precision method if it reproduces the reference cases of Annex A within their tolerances.

  • Case 1 (A.1.2). Heat conduction through half of a square column with fixed surface temperatures, which has an analytical solution. The temperatures at the 28 points of a 1 m grid inside the column must not differ from the analytical values by more than 0.1 °C.

  • Case 2 (A.1.3). Heat transfer through a section of four materials with surface resistances (Figure A.2, Table A.1). The temperatures at nine points (A to I) must not differ from the tabulated values by more than 0.1 °C, and the heat flow through the section from the tabulated value by more than 0.1 W/m.

  • Three-dimensional cases. Annex A's three-dimensional cases do not apply to a two-dimensional solver.

1.3 Case overview

Table 1.1: Cases

Case
Annex A
Behaviour tested
Quantities checked
Reference

A.1

Case 1

Conduction with fixed temperatures, analytical solution

28 temperatures

A.1.2, analytical

A.2

Case 2

Four materials, surface resistances, a metal bridge

9 temperatures and the heat flow

A.1.3, Figure A.2, Table A.1

T

Cases 1 and 2

The same models in THERM 7.8.80.0

Heat flow, temperatures, error-energy norm

THERM 7.8

1.4 Pass criteria

Verdict
Meaning

Pass

Every reference quantity within the standard's tolerance.

Fail

Any reference quantity outside it.

N/A

Outside the solver's scope (three-dimensional).

Tolerances: 0.1 °C on every temperature; 0.1 W/m on the Case 2 heat flow. Equality with THERM 7.8 is judged on THERM's displayed precision (U to 4 decimals, lengths to the whole millimetre, the error-energy norm to 2 decimals).

2. Software Configuration, General Notes

Table 2.1: Configuration

Parameter
Value

Engine

Better Building Thermx Solver 1.0

Pipeline

The detail drawing (zones, materials, boundary conditions, U-factor tags) is mapped to a THERM model, THERM's boundary generation runs, then the mesher, CONRAD and THERM's post-processing; the same path every design in the detail tool takes

Mesh

THERM's quadtree mesher, mesh parameter 6, error estimator on, error-energy-norm limit 10 %, at most 3 refinement passes (THERM 7.8's pinned settings, the settings the NFRC Simulation Manual requires)

Fixed temperatures

THERM's constant-temperature boundary condition, held by CONRAD's penalty method

Surface resistances

THERM convection boundary conditions with h = 1 / R

Temperatures at points

The finite-element solution interpolated within THERM's elements at each point (not a resampled raster)

Heat flow

Read from THERM U-factor tags as THERM reports them: U x length x delta T

Fidelity to THERM 7.8

254 of 257 regression-corpus models reproduce every reported value of THERM 7.8 end to end (the other 3 differ by one float32 step in the stored error-energy norm); 325 of 325 THERM solves reproduced from THERM's own solver input

3. Method of Assessment

3.1 Modelling each case

  1. Geometry. Case 1 from the dimensions of A.1.2. Case 2 from Figure A.2 and Table A.1 of the owner's copy of BS EN ISO 10211:2007 (A.1.3, printed page 30). The geometry is held in a case file (corpus/iso10211/case2.json) whose _source field records every reading.

  2. Materials and boundaries as the standard gives them (Appendices A and B).

  3. Read-out. Temperatures are sampled from the solved field at the reference points. For Case 2 the heat flow is read from a U-factor tag on the interior face (and, for the heat balance, a tag on the exterior face).

3.2 Solving

Each case is solved through the whole pipeline a user's design runs through (Table 2.1), by the tests named there, which fail if any point or the heat flow is outside its tolerance. The tests print every point (Tables 4.2 and 5.2 are their output).

3.3 Independent check in THERM 7.8

Case 2 was drawn in the detail tool, exported as THERM files, opened in THERM 7.8.80.0 and calculated by a scripted harness that operates THERM's own interface. Both cases are also in the detail tool as templates, with the THERM files written from the exact models of this report, so any assessor can open them in THERM 7.8 (Appendix D).

4. Case A.1: Half Square Column (Case 1)

4.1 Scenario Description

Model of Case 1

Table 4.1: Case A.1

Parameter
Value

Geometry

Half of a square column, 4 m wide by 8 m high; the right edge is the symmetry line

Material

Uniform, λ = 1 W/(m K)

Boundaries

Top edge (y = 8 m) 20 °C; left edge (x = 0) and bottom edge (y = 0) 0 °C; right edge (x = 4 m) adiabatic

Model

One polygon, three fixed-temperature boundary segments, one adiabatic

Read-out

28 points of the 1 m grid, x 1 to 4 m, y 1 to 7 m (the dots in the drawing)

Mesh

3 meshes (THERM's limit), error-energy norm 14.94 % at the last (Section 4.3)

4.2 Results

Table 4.2: Case A.1, temperatures (°C): Thermx, the standard in brackets, the difference

y \ x
1 m
2 m
3 m
4 m

7 m

9.651 (9.7) 0.049

13.371 (13.4) 0.029

14.729 (14.7) 0.029

15.094 (15.1) 0.006

6 m

5.263 (5.3) 0.037

8.646 (8.6) 0.046

10.323 (10.3) 0.023

10.829 (10.8) 0.029

5 m

3.191 (3.2) 0.009

5.618 (5.6) 0.018

7.012 (7.0) 0.012

7.478 (7.5) 0.022

4 m

2.011 (2.0) 0.011

3.631 (3.6) 0.031

4.651 (4.7) 0.049

5.000 (5.0) 0.000

3 m

1.263 (1.3) 0.037

2.310 (2.3) 0.010

2.988 (3.0) 0.012

3.222 (3.2) 0.022

2 m

0.740 (0.7) 0.040

1.364 (1.4) 0.036

1.762 (1.8) 0.038

1.910 (1.9) 0.010

1 m

0.341 (0.3) 0.041

0.628 (0.6) 0.028

0.818 (0.8) 0.018

0.885 (0.9) 0.015

All 28 points are within 0.1 °C. The largest difference is 0.049 °C, at (1, 7) and (3, 4); the mean absolute difference is 0.025 °C. The standard's values are given to 0.1 °C, so differences up to 0.05 °C are within its own rounding.

4.3 Mesh refinement

THERM's error estimator ends Case 1 at its limit of three meshes with an error-energy norm of 14.94 %, above the 10 % target, the point at which THERM 7.8 shows its warning "The maximum number of meshing iterations reached before the error target was reached." (as it does on ISO 10077-2 Figure I.6).

The cause is the corner at (0, 8) m, where the 20 °C top edge meets the 0 °C left edge: the temperature is discontinuous there, so the gradient is unbounded and the energy-norm error at that corner cannot be refined away. The error is local to the corner; the 28 reference points, the nearest 1.4 m from it, are all within 0.049 °C. This is a property of the analytical problem, not of the model.

5. Case A.2: Multi-Material Thermal Bridge (Case 2)

5.1 Scenario Description

Model of Case 2, the whole section
Model of Case 2, the left 60 mm with points A to I

Table 5.1: Case A.2

Parameter
Value

Geometry

500 mm wide (AB), 47.5 mm high (AH). Table A.1: AB 500, AC 6, CD 15, CF 5, EM 40, GJ 1.5, IM 1.5, FG - KJ 1.5

Materials

1 concrete 1.15 (the top 6 mm band); 2 wood 0.12 (the block C-D-G-F, 15 x 5 mm); 4 aluminium 230 (the bottom strip H-I-M, the left upright and the flange F-G-J-K under the wood, all 1.5 mm); 3 insulation 0.029 (the rest)

Boundaries

AB exterior, 0 °C, Rse 0.06; HI interior, 20 °C, Rsi 0.11; the two sides adiabatic

Model

Four polygons, one per material; U-factor tags Exterior on AB and Interior on HI

Read-out

The nine points A to I; the heat flow through the interior face

Mesh

1 mesh, error-energy norm 7.78 % (within the 10 % target at once)

Judgements

The 5 mm band to the right of the wood (x 15 to 500 mm, y 36.5 to 41.5 mm) carries no material number in the figure (Section 5.3)

5.2 Results

Table 5.2: Case A.2

Point
Position (x, y mm, y up from H)
Thermx (°C)
Standard (°C)
Difference

A

0, 47.5

7.174

7.1

0.074

B

500, 47.5

0.767

0.8

0.033

C

0, 41.5

7.921

7.9

0.021

D

15, 41.5

6.295

6.3

0.005

E

500, 41.5

0.827

0.8

0.027

F

0, 36.5

16.394

16.4

0.006

G

15, 36.5

16.321

16.3

0.021

H

0, 0

16.754

16.8

0.046

I

500, 0

18.330

18.3

0.030

Heat flow

9.538 W/m

9.5 W/m

0.038 W/m

All nine temperatures are within 0.1 °C (largest 0.074 °C, at A) and the heat flow within 0.1 W/m. The heat flow is THERM's tag result: U 0.9538 W/(m2 K) over 500 mm with delta T 20 K. Points on the outline (A, B, C, E, H, I) are read one sampling step (1 mm in x, 0.5 mm in y) inside the section, since exactly on the edge the sampler can fall outside the mesh.

5.3 The unlabelled band

Figure A.2 numbers the top band 1, the block 2, the large region 3 and the thin strips 4, but leaves the 5 mm band to the right of the wood unnumbered. Solving it both ways settles it: as insulation every reference temperature is met and the heat flow is 9.54 W/m; as concrete the points miss by up to 2.2 °C (D 8.46 against 6.3) and the heat flow is 12.1 W/m. The band is insulation: the wood block sits in the insulation's top-left corner, under the concrete.

6. Agreement with THERM 7.8

6.1 The same model in THERM 7.8

Table 6.1: Case A.2, THERM 7.8.80.0 against the Better Building Thermx Solver 1.0

Quantity

THERM 7.8, .THM

THERM 7.8, .thmx

Thermx, same files

Equal

Opens

Without a message

Without a message

Exterior tag

U 0.9538 over 500 mm, delta T 20.0

The same

U 0.953790 over 500 mm, delta T 20

yes

Interior tag

U 0.9538 over 500 mm, delta T 20.0

The same

U 0.953790 over 500 mm, delta T 20

yes

Heat flow

9.538 W/m

9.538 W/m

9.5379 W/m

yes

Error-energy norm

7.78 %

7.78 %

7.7796 %

yes

Max temperature

18.33 °C

18.33 °C

18.33 °C

yes

Min temperature

0.742509 °C

0.742509 °C

0.742509 °C

yes

The template's THERM files, written from the exact model of Section 5, give the same values in the Better Building Thermx Solver 1.0. THERM's maximum, 18.33 °C, equals point I (18.330 °C); its minimum, 0.7425 °C, is just below point B (0.767 °C), which is read 1 mm inside the section.

6.2 Heat balance

In a steady state the heat entering through the interior face equals the heat leaving through the exterior face. In THERM 7.8 and in the Better Building Thermx Solver 1.0 both tags give 0.9538 W/(m2 K) over 500 mm: 9.538 W/m in and 9.538 W/m out.

7. Summary of Results

Table 7.1: Summary

Case
Behaviour tested
Headline agreement
Thermx = Better Building Thermx Solver 1.0
Verdict

A.1

Half square column, fixed temperatures

28 of 28 points within 0.1 °C (largest 0.049 °C)

Not yet run in THERM

Pass

A.2

Multi-material section with surface resistances

9 of 9 points within 0.1 °C (largest 0.074 °C); heat flow 9.538 against 9.5 W/m

Yes, both file formats

Pass

3-D cases

Three-dimensional

Not applicable to a two-dimensional solver

Out of scope

N/A

Both two-dimensional cases of ISO 10211:2007 Annex A pass, so the solver is a two-dimensional steady-state high precision method in the sense of A.1.1.

Appendix A: Material Property Tabulations

Case
Material
λ W/(m K)

A.1

Uniform

1.0

A.2

1 Concrete

1.15

A.2

2 Wood

0.12

A.2

3 Insulation

0.029

A.2

4 Aluminium

230

Appendix B: Boundary-Condition Data

Case
Surface
Temperature
Resistance
THERM boundary condition

A.1

Top edge

20 °C

Constant temperature

A.1

Left and bottom edges

0 °C

Constant temperature

A.1

Right edge (symmetry)

Adiabatic

Adiabatic

A.2

AB, exterior

0 °C

Rse 0.06 m2 K/W

Convection, h 16.67 W/(m2 K)

A.2

HI, interior

20 °C

Rsi 0.11 m2 K/W

Convection, h 9.09 W/(m2 K)

A.2

Sides

Adiabatic

Adiabatic

Appendix C: Reference Point Coordinates

Case
Points
Coordinates

A.1

28 grid points

x = 1, 2, 3, 4 m; y = 1 to 7 m, origin at the bottom-left corner, y up

A.2

A, B

(0, 47.5), (500, 47.5) mm: the exterior face

A.2

C, D, E

(0, 41.5), (15, 41.5), (500, 41.5) mm: the underside of the concrete

A.2

F, G

(0, 36.5), (15, 36.5) mm: the underside of the wood

A.2

H, I

(0, 0), (500, 0) mm: the interior face