ISO 10211 Thermal Bridge Validation Report
Software Version: Better Building Thermx Solver 1.0 I Date of Testing: 28/10/26 I Report Version: 1.0 I Prepared by Darren O'Dea
1. Purpose and Scope
1.1 Introduction
This report records how the two-dimensional solver behind the Better Building detail tool performs against the validation cases of ISO 10211:2007 Annex A. It is written for third-party assurance: each case states how it was modelled, the result at every reference point against the standard's value, and the same model solved in LBNL THERM 7.8 as an independent check.
The detail tool solves with Better Building Thermx Solver 1.0, an independent finite-element solver and checked against THERM 7.8 itself. Window frames are reported separately in the ISO 10077-2 Window Frame Validation Report (version 1.0), and the ISO 14683 junctions in the ISO 10211 / ISO 14683 / ISO 10077-2 thermal-bridge validation report (version 2.0).
Two references are used:
The standard's values: ISO 10211:2007 Annex A: the analytical temperatures of Case 1 and the tabulated temperatures and heat flow of Case 2.
THERM 7.8 itself: the case models are exported from the detail tool as THERM files and solved in the installed THERM 7.8.80.0, so the report also shows whether Better Building Thermx Solver 1.0 gives THERM's own answer on the same model.
1.2 The standard
Classification (A.1.1). A two-dimensional calculation method is a steady-state high precision method if it reproduces the reference cases of Annex A within their tolerances.
Case 1 (A.1.2). Heat conduction through half of a square column with fixed surface temperatures, which has an analytical solution. The temperatures at the 28 points of a 1 m grid inside the column must not differ from the analytical values by more than 0.1 °C.
Case 2 (A.1.3). Heat transfer through a section of four materials with surface resistances (Figure A.2, Table A.1). The temperatures at nine points (A to I) must not differ from the tabulated values by more than 0.1 °C, and the heat flow through the section from the tabulated value by more than 0.1 W/m.
Three-dimensional cases. Annex A's three-dimensional cases do not apply to a two-dimensional solver.
1.3 Case overview
Table 1.1: Cases
A.1
Case 1
Conduction with fixed temperatures, analytical solution
28 temperatures
A.1.2, analytical
A.2
Case 2
Four materials, surface resistances, a metal bridge
9 temperatures and the heat flow
A.1.3, Figure A.2, Table A.1
T
Cases 1 and 2
The same models in THERM 7.8.80.0
Heat flow, temperatures, error-energy norm
THERM 7.8
1.4 Pass criteria
Pass
Every reference quantity within the standard's tolerance.
Fail
Any reference quantity outside it.
N/A
Outside the solver's scope (three-dimensional).
Tolerances: 0.1 °C on every temperature; 0.1 W/m on the Case 2 heat flow. Equality with THERM 7.8 is judged on THERM's displayed precision (U to 4 decimals, lengths to the whole millimetre, the error-energy norm to 2 decimals).
2. Software Configuration, General Notes
Table 2.1: Configuration
Engine
Better Building Thermx Solver 1.0
Pipeline
The detail drawing (zones, materials, boundary conditions, U-factor tags) is mapped to a THERM model, THERM's boundary generation runs, then the mesher, CONRAD and THERM's post-processing; the same path every design in the detail tool takes
Mesh
THERM's quadtree mesher, mesh parameter 6, error estimator on, error-energy-norm limit 10 %, at most 3 refinement passes (THERM 7.8's pinned settings, the settings the NFRC Simulation Manual requires)
Fixed temperatures
THERM's constant-temperature boundary condition, held by CONRAD's penalty method
Surface resistances
THERM convection boundary conditions with h = 1 / R
Temperatures at points
The finite-element solution interpolated within THERM's elements at each point (not a resampled raster)
Heat flow
Read from THERM U-factor tags as THERM reports them: U x length x delta T
Fidelity to THERM 7.8
254 of 257 regression-corpus models reproduce every reported value of THERM 7.8 end to end (the other 3 differ by one float32 step in the stored error-energy norm); 325 of 325 THERM solves reproduced from THERM's own solver input
3. Method of Assessment
3.1 Modelling each case
Geometry. Case 1 from the dimensions of A.1.2. Case 2 from Figure A.2 and Table A.1 of the owner's copy of BS EN ISO 10211:2007 (A.1.3, printed page 30). The geometry is held in a case file (corpus/iso10211/case2.json) whose
_sourcefield records every reading.Materials and boundaries as the standard gives them (Appendices A and B).
Read-out. Temperatures are sampled from the solved field at the reference points. For Case 2 the heat flow is read from a U-factor tag on the interior face (and, for the heat balance, a tag on the exterior face).
3.2 Solving
Each case is solved through the whole pipeline a user's design runs through (Table 2.1), by the tests named there, which fail if any point or the heat flow is outside its tolerance. The tests print every point (Tables 4.2 and 5.2 are their output).
3.3 Independent check in THERM 7.8
Case 2 was drawn in the detail tool, exported as THERM files, opened in THERM 7.8.80.0 and calculated by a scripted harness that operates THERM's own interface. Both cases are also in the detail tool as templates, with the THERM files written from the exact models of this report, so any assessor can open them in THERM 7.8 (Appendix D).
4. Case A.1: Half Square Column (Case 1)
4.1 Scenario Description
Table 4.1: Case A.1
Geometry
Half of a square column, 4 m wide by 8 m high; the right edge is the symmetry line
Material
Uniform, λ = 1 W/(m K)
Boundaries
Top edge (y = 8 m) 20 °C; left edge (x = 0) and bottom edge (y = 0) 0 °C; right edge (x = 4 m) adiabatic
Model
One polygon, three fixed-temperature boundary segments, one adiabatic
Read-out
28 points of the 1 m grid, x 1 to 4 m, y 1 to 7 m (the dots in the drawing)
Mesh
3 meshes (THERM's limit), error-energy norm 14.94 % at the last (Section 4.3)
4.2 Results
Table 4.2: Case A.1, temperatures (°C): Thermx, the standard in brackets, the difference
7 m
9.651 (9.7) 0.049
13.371 (13.4) 0.029
14.729 (14.7) 0.029
15.094 (15.1) 0.006
6 m
5.263 (5.3) 0.037
8.646 (8.6) 0.046
10.323 (10.3) 0.023
10.829 (10.8) 0.029
5 m
3.191 (3.2) 0.009
5.618 (5.6) 0.018
7.012 (7.0) 0.012
7.478 (7.5) 0.022
4 m
2.011 (2.0) 0.011
3.631 (3.6) 0.031
4.651 (4.7) 0.049
5.000 (5.0) 0.000
3 m
1.263 (1.3) 0.037
2.310 (2.3) 0.010
2.988 (3.0) 0.012
3.222 (3.2) 0.022
2 m
0.740 (0.7) 0.040
1.364 (1.4) 0.036
1.762 (1.8) 0.038
1.910 (1.9) 0.010
1 m
0.341 (0.3) 0.041
0.628 (0.6) 0.028
0.818 (0.8) 0.018
0.885 (0.9) 0.015
All 28 points are within 0.1 °C. The largest difference is 0.049 °C, at (1, 7) and (3, 4); the mean absolute difference is 0.025 °C. The standard's values are given to 0.1 °C, so differences up to 0.05 °C are within its own rounding.
4.3 Mesh refinement
THERM's error estimator ends Case 1 at its limit of three meshes with an error-energy norm of 14.94 %, above the 10 % target, the point at which THERM 7.8 shows its warning "The maximum number of meshing iterations reached before the error target was reached." (as it does on ISO 10077-2 Figure I.6).
The cause is the corner at (0, 8) m, where the 20 °C top edge meets the 0 °C left edge: the temperature is discontinuous there, so the gradient is unbounded and the energy-norm error at that corner cannot be refined away. The error is local to the corner; the 28 reference points, the nearest 1.4 m from it, are all within 0.049 °C. This is a property of the analytical problem, not of the model.
5. Case A.2: Multi-Material Thermal Bridge (Case 2)
5.1 Scenario Description
Table 5.1: Case A.2
Geometry
500 mm wide (AB), 47.5 mm high (AH). Table A.1: AB 500, AC 6, CD 15, CF 5, EM 40, GJ 1.5, IM 1.5, FG - KJ 1.5
Materials
1 concrete 1.15 (the top 6 mm band); 2 wood 0.12 (the block C-D-G-F, 15 x 5 mm); 4 aluminium 230 (the bottom strip H-I-M, the left upright and the flange F-G-J-K under the wood, all 1.5 mm); 3 insulation 0.029 (the rest)
Boundaries
AB exterior, 0 °C, Rse 0.06; HI interior, 20 °C, Rsi 0.11; the two sides adiabatic
Model
Four polygons, one per material; U-factor tags Exterior on AB and Interior on HI
Read-out
The nine points A to I; the heat flow through the interior face
Mesh
1 mesh, error-energy norm 7.78 % (within the 10 % target at once)
Judgements
The 5 mm band to the right of the wood (x 15 to 500 mm, y 36.5 to 41.5 mm) carries no material number in the figure (Section 5.3)
5.2 Results
Table 5.2: Case A.2
A
0, 47.5
7.174
7.1
0.074
B
500, 47.5
0.767
0.8
0.033
C
0, 41.5
7.921
7.9
0.021
D
15, 41.5
6.295
6.3
0.005
E
500, 41.5
0.827
0.8
0.027
F
0, 36.5
16.394
16.4
0.006
G
15, 36.5
16.321
16.3
0.021
H
0, 0
16.754
16.8
0.046
I
500, 0
18.330
18.3
0.030
Heat flow
9.538 W/m
9.5 W/m
0.038 W/m
All nine temperatures are within 0.1 °C (largest 0.074 °C, at A) and the heat flow within 0.1 W/m. The heat flow is THERM's tag result: U 0.9538 W/(m2 K) over 500 mm with delta T 20 K. Points on the outline (A, B, C, E, H, I) are read one sampling step (1 mm in x, 0.5 mm in y) inside the section, since exactly on the edge the sampler can fall outside the mesh.
5.3 The unlabelled band
Figure A.2 numbers the top band 1, the block 2, the large region 3 and the thin strips 4, but leaves the 5 mm band to the right of the wood unnumbered. Solving it both ways settles it: as insulation every reference temperature is met and the heat flow is 9.54 W/m; as concrete the points miss by up to 2.2 °C (D 8.46 against 6.3) and the heat flow is 12.1 W/m. The band is insulation: the wood block sits in the insulation's top-left corner, under the concrete.
6. Agreement with THERM 7.8
6.1 The same model in THERM 7.8
Table 6.1: Case A.2, THERM 7.8.80.0 against the Better Building Thermx Solver 1.0
Quantity
THERM 7.8, .THM
THERM 7.8, .thmx
Thermx, same files
Equal
Opens
Without a message
Without a message
Exterior tag
U 0.9538 over 500 mm, delta T 20.0
The same
U 0.953790 over 500 mm, delta T 20
yes
Interior tag
U 0.9538 over 500 mm, delta T 20.0
The same
U 0.953790 over 500 mm, delta T 20
yes
Heat flow
9.538 W/m
9.538 W/m
9.5379 W/m
yes
Error-energy norm
7.78 %
7.78 %
7.7796 %
yes
Max temperature
18.33 °C
18.33 °C
18.33 °C
yes
Min temperature
0.742509 °C
0.742509 °C
0.742509 °C
yes
The template's THERM files, written from the exact model of Section 5, give the same values in the Better Building Thermx Solver 1.0. THERM's maximum, 18.33 °C, equals point I (18.330 °C); its minimum, 0.7425 °C, is just below point B (0.767 °C), which is read 1 mm inside the section.
6.2 Heat balance
In a steady state the heat entering through the interior face equals the heat leaving through the exterior face. In THERM 7.8 and in the Better Building Thermx Solver 1.0 both tags give 0.9538 W/(m2 K) over 500 mm: 9.538 W/m in and 9.538 W/m out.
7. Summary of Results
Table 7.1: Summary
A.1
Half square column, fixed temperatures
28 of 28 points within 0.1 °C (largest 0.049 °C)
Not yet run in THERM
Pass
A.2
Multi-material section with surface resistances
9 of 9 points within 0.1 °C (largest 0.074 °C); heat flow 9.538 against 9.5 W/m
Yes, both file formats
Pass
3-D cases
Three-dimensional
Not applicable to a two-dimensional solver
Out of scope
N/A
Both two-dimensional cases of ISO 10211:2007 Annex A pass, so the solver is a two-dimensional steady-state high precision method in the sense of A.1.1.
Appendix A: Material Property Tabulations
A.1
Uniform
1.0
A.2
1 Concrete
1.15
A.2
2 Wood
0.12
A.2
3 Insulation
0.029
A.2
4 Aluminium
230
Appendix B: Boundary-Condition Data
A.1
Top edge
20 °C
Constant temperature
A.1
Left and bottom edges
0 °C
Constant temperature
A.1
Right edge (symmetry)
Adiabatic
Adiabatic
A.2
AB, exterior
0 °C
Rse 0.06 m2 K/W
Convection, h 16.67 W/(m2 K)
A.2
HI, interior
20 °C
Rsi 0.11 m2 K/W
Convection, h 9.09 W/(m2 K)
A.2
Sides
Adiabatic
Adiabatic
Appendix C: Reference Point Coordinates
A.1
28 grid points
x = 1, 2, 3, 4 m; y = 1 to 7 m, origin at the bottom-left corner, y up
A.2
A, B
(0, 47.5), (500, 47.5) mm: the exterior face
A.2
C, D, E
(0, 41.5), (15, 41.5), (500, 41.5) mm: the underside of the concrete
A.2
F, G
(0, 36.5), (15, 36.5) mm: the underside of the wood
A.2
H, I
(0, 0), (500, 0) mm: the interior face